{"id":50033,"date":"2026-06-02T13:33:47","date_gmt":"2026-06-02T12:33:47","guid":{"rendered":"https:\/\/surespancovers.com\/us\/fire-rated-access-doors-hour-ratings\/"},"modified":"2026-06-02T13:33:47","modified_gmt":"2026-06-02T12:33:47","slug":"fire-rated-access-doors-hour-ratings","status":"publish","type":"post","link":"https:\/\/surespancovers.com\/us\/fire-rated-access-doors-hour-ratings\/","title":{"rendered":"Fire Rated Access Doors: What a 1 Hour or 2 Hour Rating Means"},"content":{"rendered":"<p>A 1 hour or 2 hour rating on a fire rated access door states how long the door and its frame, tested together in a standard fire test, met the test&#8217;s criteria. It only means something together with three other facts: which test standard was used, which criteria the hours apply to, and the size and wall type that were tested. In the United States, walls and floors are rated in hours from assembly tests such as UL 263, Fire Tests of Building Construction and Materials, and the standard for fire doors and other opening protectives is NFPA 80.<\/p>\n<p>This guide is about access doors and riser doors in fire-rated walls. Fire rated roof hatches are covered in <a href=\"https:\/\/surespancovers.com\/us\/fire-rating-standards-for-roof-hatches-in-the-us-a-case-for-european-compliance\/\">Fire Rating Standards for Roof Hatches in the US<\/a>.<\/p>\n<h2>Why does an access door in a rated wall need its own rating?<\/h2>\n<p>A fire-rated wall or floor holds a fire in one part of the building for a set time. Every opening in it, whether a door, a duct or a service access door, is a weak point unless the opening is protected for the same purpose. An ordinary access panel in a 2 hour shaft wall gives fire a way into the shaft. A fire rated access door is tested as a complete unit, door leaf and frame, so that the opening is not the first part of the wall to fail.<\/p>\n<p>The rating each wall or floor needs, and the protection its openings need, are set by the building code your jurisdiction has adopted and by the fire protection design for the project. The authority having jurisdiction decides what evidence it accepts for a given door.<\/p>\n<h2>What does the hour rating measure?<\/h2>\n<p>A fire resistance test exposes a sample to a standard fire for a set time and checks it against stated criteria. UL 263 describes its purpose as evaluating the length of time that the assemblies it covers will contain a fire or retain their structural integrity, or both, during a predetermined test exposure. It includes measurement of the transmission of heat through the assembly, and it expresses results in hours, for example a 2-hour rating.<\/p>\n<p>European tests split the criteria and report each one separately. The two that matter most for an access door are:<\/p>\n<table class=\"mtr-table mtr-thead-th\">\n<thead>\n<tr>\n<th data-mtr-content=\"Criterion\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Criterion<\/div><\/th>\n<th data-mtr-content=\"What it asks\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">What it asks<\/div><\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td data-mtr-content=\"Criterion\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Integrity<\/div><\/td>\n<td data-mtr-content=\"What it asks\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Does the door stop flames and hot gases getting through gaps and cracks?<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Criterion\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Insulation<\/div><\/td>\n<td data-mtr-content=\"What it asks\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Does the unexposed face stay cool enough that it will not set fire to things on the safe side?<\/div><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>A door can hold its integrity for 2 hours and still get hot on the far side. So &#8220;2 hour&#8221; on its own does not tell you whether heat transmission was part of the result. Read the sheet or the test report for the criterion.<\/p>\n<h2>What do Surespan&#8217;s riser door sheets state?<\/h2>\n<p>The five Surespan riser door sheets below state tests to the European fire resistance test standard for doors, EN 1634-1. Each sheet states the hours for integrity, in a wall application, up to a maximum tested size:<\/p>\n<table class=\"mtr-table mtr-thead-th\">\n<thead>\n<tr>\n<th data-mtr-content=\"Model\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Model<\/div><\/th>\n<th data-mtr-content=\"Rating as printed\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Rating as printed<\/div><\/th>\n<th data-mtr-content=\"Maximum tested size\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Maximum tested size<\/div><\/th>\n<th data-mtr-content=\"Test standards named\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Test standards named<\/div><\/th>\n<th data-mtr-content=\"Smoke\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Smoke<\/div><\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td data-mtr-content=\"Model\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">WAP-C-FR120-RF-3WL<\/div><\/td>\n<td data-mtr-content=\"Rating as printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2 Hour, integrity<\/div><\/td>\n<td data-mtr-content=\"Maximum tested size\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2400X900mm (94.5 x 35.4 in)<\/div><\/td>\n<td data-mtr-content=\"Test standards named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">BSEN 1634-1: 2008 and BSEN 1363-1: 1999<\/div><\/td>\n<td data-mtr-content=\"Smoke\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Not smoke tested<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Model\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">WAP-C-RF-FR120-3WL-36DB<\/div><\/td>\n<td data-mtr-content=\"Rating as printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2 Hour, integrity<\/div><\/td>\n<td data-mtr-content=\"Maximum tested size\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2400X900mm (94.5 x 35.4 in)<\/div><\/td>\n<td data-mtr-content=\"Test standards named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">BSEN 1634-1: 2008 and BSEN 1363-1: 1999<\/div><\/td>\n<td data-mtr-content=\"Smoke\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Smoke tested to 25pa, BS EN 1634-3: 2004<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Model\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">WAP-C-RF-FR120-3WL-DD (double door)<\/div><\/td>\n<td data-mtr-content=\"Rating as printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2 Hour, integrity<\/div><\/td>\n<td data-mtr-content=\"Maximum tested size\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2400x1800mm (94.5 x 70.9 in)<\/div><\/td>\n<td data-mtr-content=\"Test standards named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">BSEN 1634-1: 2014 and BSEN 1363-1: 2012<\/div><\/td>\n<td data-mtr-content=\"Smoke\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Not smoke tested<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Model\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">WAP-C-WD-RF-FR120-MD-3WL-2D-AT-36DB (airtight)<\/div><\/td>\n<td data-mtr-content=\"Rating as printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2 Hour, integrity, from both sides<\/div><\/td>\n<td data-mtr-content=\"Maximum tested size\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">2400X1800mm (94.5 x 70.9 in)<\/div><\/td>\n<td data-mtr-content=\"Test standards named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">BSEN 1634-1: 2014 and BSEN 1363-1: 2012<\/div><\/td>\n<td data-mtr-content=\"Smoke\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Smoke tested, BS EN 1634-3: 2004<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Model\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">WAP-C-RF-3WL-33A-B1 (acoustic)<\/div><\/td>\n<td data-mtr-content=\"Rating as printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">1 Hour, integrity<\/div><\/td>\n<td data-mtr-content=\"Maximum tested size\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">1900x650mm (74.8 x 25.6 in)<\/div><\/td>\n<td data-mtr-content=\"Test standards named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">BSEN 1634-1: 2014<\/div><\/td>\n<td data-mtr-content=\"Smoke\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Smoke tested, BS EN 1634-3: 2004<\/div><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>All five sheets give integrity only. They name no insulation value and no classification standard. All five state a wall application, so none of them is evidence for a door in a ceiling or floor. The doors are made from Zintec steel and installed into a joint-less plasterboard wall system, and the 2 hour single door sheet lists intumescent seals.<\/p>\n<p>These are European test results. The sheets do not claim a UL listing or a UL 263 rating, and they do not state that a door meets NFPA 80 or the building code. Whether an EN 1634-1 test is accepted for your wall is the decision of the authority having jurisdiction, so raise it early.<\/p>\n<h2>What evidence should you ask for?<\/h2>\n<ol>\n<li>The test or classification report, not only the data sheet, with the criteria the hours apply to.<\/li>\n<li>The tested size range, and confirmation that your door is inside it. 2400X900mm and 2400x1800mm are maximum tested sizes, not standard sizes.<\/li>\n<li>The wall construction that was tested, and confirmation that your wall matches it.<\/li>\n<li>The fire side: whether the door was tested from one side or, as the airtight door sheet states, from both sides.<\/li>\n<li>Smoke test results, where the wall also has to resist smoke.<\/li>\n<li>Installation instructions. On the 2 hour single door sheet, the structural opening is at least 7mm (0.3 in) larger than the panel size, back of frame size, so a 600x600mm (23.6 x 23.6 in) panel needs a 607x607mm (23.9 x 23.9 in) hole, and intumescent acrylic mastic, nominally 5mm (0.2 in) wide, is applied on both faces of the frame.<\/li>\n<\/ol>\n<p>A door is only as good as its installation. The tested result assumes the frame is fixed and sealed into the wall as it was in the test.<\/p>\n<h2>When is a riser door not the right product?<\/h2>\n<p>All five sheets above are wall doors. For access through a fire-rated floor, use a product tested in a floor (see the <a href=\"https:\/\/surespancovers.com\/us\/product-category\/floor-hatches\/\">floor hatch range<\/a> and ask for the floor test evidence), and for the roof see the <a href=\"https:\/\/surespancovers.com\/us\/product\/fire-rated-roof-hatch\/\">Fire Rated Roof Hatch<\/a>. Where only a small inspection opening is needed, a fire rated access panel may suit better: see <a href=\"https:\/\/surespancovers.com\/us\/access-panels\/\">Access Panels<\/a>.<\/p>\n<h2>Frequently asked questions<\/h2>\n<h3>Is a 2 hour access door the same as a 2 hour wall?<\/h3>\n<p>Not automatically. The wall&#8217;s rating comes from the test of the wall assembly. The door&#8217;s rating comes from the test of the door and the criteria it was assessed on. Check that the door&#8217;s result covers what the wall&#8217;s rating requires.<\/p>\n<h3>Does a fire rated access door need a smoke rating?<\/h3>\n<p>Only where the project asks for it. Some of Surespan&#8217;s riser doors are smoke tested to BS EN 1634-3: 2004 and some are not, as the table shows.<\/p>\n<h3>What size can a fire rated riser door be?<\/h3>\n<p>Up to the maximum tested size on its sheet: for example 2400X900mm for the single 2 hour door and 2400x1800mm for the double door.<\/p>\n<h3>Are Surespan riser doors UL listed?<\/h3>\n<p>The sheets do not state a UL listing. They state EN 1634-1 tests for integrity. Agree the acceptable evidence with the authority having jurisdiction.<\/p>\n<p>See the full range of <a href=\"https:\/\/surespancovers.com\/us\/riser-doors\/\">Riser Doors<\/a> and the <a href=\"https:\/\/surespancovers.com\/us\/resource-centre\/riser-door-resources\/\">riser door resources<\/a>. To ask about a specification, use the <a href=\"https:\/\/surespancovers.com\/us\/contact-us\/\">Surespan contact page<\/a>.<\/p>\n<h2>Sources<\/h2>\n<ul>\n<li>Surespan data sheet &#8220;Fire-Rated Riser Doors&#8221; WAP-C-FR120-RF-3WL, July 2021: rating, size, test standards, seals, fitting. Range: <a href=\"https:\/\/surespancovers.com\/us\/riser-doors\/\">Riser Doors<\/a>.<\/li>\n<li>Surespan data sheet &#8220;Fire-Rated Riser Doors&#8221; WAP-C-RF-FR120-3WL-36DB, July 2021: rating, size, test standards, smoke test.<\/li>\n<li>Surespan data sheet &#8220;Fire-Rated Riser Doors&#8221; WAP-C-RF-FR120-3WL-DD, July 2021: rating, size, test standards.<\/li>\n<li>Surespan data sheet &#8220;Airtight Riser Doors&#8221; WAP-C-WD-RF-FR120-MD-3WL-2D-AT-36DB, July 2021: rating from both sides, size, smoke test.<\/li>\n<li>Surespan data sheet &#8220;Acoustic-Rated Riser Doors&#8221; WAP-C-RF-3WL-33A-B1, September 2021: rating, size, smoke test. Downloads: <a href=\"https:\/\/surespancovers.com\/us\/resource-centre\/riser-door-resources\/\">Riser Door Resources<\/a>.<\/li>\n<li>UL 263, Fire Tests of Building Construction and Materials, Edition 14, <a href=\"https:\/\/www.shopulstandards.com\/ProductDetail.aspx?productId=UL263\" target=\"_blank\" rel=\"noopener\">shopulstandards.com<\/a>.<\/li>\n<li>NFPA 80, Standard for Fire Doors and Other Opening Protectives, <a href=\"https:\/\/www.nfpa.org\/product\/nfpa-80-standard\/p0080code\" target=\"_blank\" rel=\"noopener\">nfpa.org<\/a>.<\/li>\n<\/ul>\n","protected":false},"excerpt":{"rendered":"<p>What the hour rating on a fire rated access door or riser door tells you, what it leaves out, and which test documents to ask for.<\/p>\n","protected":false},"author":6,"featured_media":47989,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"content-type":"","_ayudawp_aiss_exclude":false,"_ayudawp_aiss_exclude_summary":false,"_ayudawp_aiss_summary":"A 1 hour or 2 hour rating on a fire rated access door states how long the door and its frame, tested together in a standard fire test, met the test's criteria. For access through a fire-rated floor, use a product tested in a floor (see the floor hatch range and ask for the floor test evidence), and for the roof see the Fire Rated Roof Hatch. Surespan data sheet \"Fire-Rated Riser Doors\" WAP-C-RF-FR120-3WL-36DB, July 2021: rating, size, test standards, smoke test.","_ayudawp_aiss_summary_provider":"extractive","_ayudawp_aiss_summary_hash":"9a3bbdc7a85c61f408beeaad5c65875263692680","footnotes":""},"categories":[525],"tags":[],"country":[],"product-supplied":[],"class_list":["post-50033","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-articles"],"acf":[],"publishpress_future_workflow_manual_trigger":{"enabledWorkflows":[]},"_links":{"self":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts\/50033","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/users\/6"}],"replies":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/comments?post=50033"}],"version-history":[{"count":0,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts\/50033\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/media\/47989"}],"wp:attachment":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/media?parent=50033"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/categories?post=50033"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/tags?post=50033"},{"taxonomy":"country","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/country?post=50033"},{"taxonomy":"product-supplied","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/product-supplied?post=50033"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}