{"id":50034,"date":"2026-07-13T14:15:43","date_gmt":"2026-07-13T13:15:43","guid":{"rendered":"https:\/\/surespancovers.com\/us\/fire-rated-floor-access-doors\/"},"modified":"2026-07-13T14:15:43","modified_gmt":"2026-07-13T13:15:43","slug":"fire-rated-floor-access-doors","status":"publish","type":"post","link":"https:\/\/surespancovers.com\/us\/fire-rated-floor-access-doors\/","title":{"rendered":"Fire Rated Floor Access Doors: What the Test Evidence Should Show"},"content":{"rendered":"<p>A fire rated floor access door, or fire rated floor hatch, is a floor door built to stop fire passing through an opening in a fire-resistance-rated floor for a stated time. Its rating is only as good as the test evidence behind it: before you accept &#8220;rated up to 4 hours&#8221;, ask which standard it was tested to, which performance criterion the time refers to, from which side the fire was applied, and whether the tested size and orientation match your opening.<\/p>\n<p>In US practice, fire resistance is stated in hours. UL 263, Fire Tests of Building Construction and Materials, says the performance of its standard fire tests may be &#8220;expressed as &#8216;2-hour,&#8217; &#8216;6-hour,&#8217; &#8216;1\/2-hour,&#8217; or the like&#8221;. Which rating an opening in a rated floor needs, and what evidence the code official accepts, depends on the code adopted for your project.<\/p>\n<h2>Why is &#8220;4-hour rated&#8221; not a complete specification?<\/h2>\n<p>A fire rating describes how a tested construction performed under stated conditions. The same product can perform differently at another size, in another orientation or with the fire on the other side. Before a manufacturer can confirm an evidence route, the design team should settle:<\/p>\n<ul>\n<li>whether the requirement is integrity only, or integrity and insulation;<\/li>\n<li>the fire test or classification standard that applies;<\/li>\n<li>the fire exposure direction, from below, from above or both;<\/li>\n<li>whether the tested construction covers the required size;<\/li>\n<li>whether the frame, hinges, seals, insulation and hardware match the tested or assessed construction;<\/li>\n<li>whether the surrounding slab and embedded frame form part of the fire-resisting line;<\/li>\n<li>whether operation, locking, controls or monitoring contacts introduce untested penetrations or changes.<\/li>\n<\/ul>\n<h2>What evidence is there, from strongest to weakest?<\/h2>\n<ol>\n<li><strong>Direct third-party test evidence.<\/strong> The product, or a very close tested specimen, was physically tested to a relevant standard. Size, orientation, support, hardware and fire direction all matter.<\/li>\n<li><strong>Classification, extended application or expert judgement.<\/strong> For bespoke sizes, a test may not match the project exactly. In Europe the route can be an extended application (EXAP) of test results, a classification report or an independent expert judgement. Describe it honestly: an assessed size is not a directly tested size.<\/li>\n<li><strong>Engineering calculation.<\/strong> For loads, anchorage and frame support, structural calculation covers what fire testing does not.<\/li>\n<li><strong>Bespoke project validation.<\/strong> Some combinations, such as a large fire rated hatch that must also meet security and seismic demands, may need project-specific design, assessment or testing.<\/li>\n<\/ol>\n<h2>What do Surespan&#8217;s floor door data sheets state?<\/h2>\n<table class=\"mtr-table mtr-thead-th\">\n<thead>\n<tr>\n<th data-mtr-content=\"Product\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Product<\/div><\/th>\n<th data-mtr-content=\"Fire statement on the data sheet\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Fire statement on the data sheet<\/div><\/th>\n<th data-mtr-content=\"Standard named\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Standard named<\/div><\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td data-mtr-content=\"Product\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">HIAC recessed floor door<\/div><\/td>\n<td data-mtr-content=\"Fire statement on the data sheet\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Can be fire rated from the underside only, up to 4 hours<\/div><\/td>\n<td data-mtr-content=\"Standard named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">BS EN 1634-1: 2008 and BS EN 1363-1: 1999<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Product\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">SAC flush floor door<\/div><\/td>\n<td data-mtr-content=\"Fire statement on the data sheet\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Can be fire rated from the underside only, up to 4 hours<\/div><\/td>\n<td data-mtr-content=\"Standard named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">BS EN 1634-1: 2008 and BS EN 1363-1: 1999<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Product\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">EHDC heavy duty floor door<\/div><\/td>\n<td data-mtr-content=\"Fire statement on the data sheet\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Can be fire rated up to 4 hours<\/div><\/td>\n<td data-mtr-content=\"Standard named\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">None named on the sheet<\/div><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Three points follow. First, these are European test standards, not US ones: the sheets do not state a UL listing or a US classification, and none should be assumed. Second, the sheets do not name the performance criterion, so ask whether the hours refer to integrity, insulation or both. Third, the HIAC and SAC ratings are from the underside only; if fire from above matters in your building, raise it before you specify.<\/p>\n<p>There is also an orientation question. BS EN 1634-1 is a fire resistance test standard for door and shutter assemblies and openable windows designed for installation within openings in vertical separating elements. A floor door is horizontal, so confirm that the test evidence, classification or assessment suits the actual horizontal installation. The sheets cite the 2008 and 1999 editions; the current editions are BS EN 1634-1:2014+A1:2018 and BS EN 1363-1:2020, and a project specification may ask for evidence aligned to them.<\/p>\n<p>Ask Surespan for the test or classification report, the tested size and the fire direction for the unit you specify, and give them to your fire engineer and the code official. For how European fire testing compares on roof hatches, see <a href=\"https:\/\/surespancovers.com\/us\/fire-rating-standards-for-roof-hatches-in-the-us-a-case-for-european-compliance\/\">Fire Rating Standards for Roof Hatches in the US<\/a>.<\/p>\n<h2>What about loads, seismic and security?<\/h2>\n<p>A fire rated floor door usually has to carry load too, and each demand needs its own evidence.<\/p>\n<ul>\n<li><strong>Loads.<\/strong> The HIAC and SAC sheets list pedestrian loads of 5\u00a0kN\/m\u00b2 (approx. 104 psf) and 10\u00a0kN\/m\u00b2 (approx. 209 psf), and wheel load classes from W3 15\u00a0kN to W8 158\u00a0kN wheel load. A uniformly distributed load is not a wheel or point load: give the structural engineer the real load case, and let the engineer decide what the floor door and its frame must carry.<\/li>\n<li><strong>Seismic.<\/strong> A phrase such as &#8220;seismic zone&#8221; is not a design basis. The structural engineer should set the design inputs under the code adopted for the project, including whether the door only has to stay fixed and closed or must still open after the event.<\/li>\n<li><strong>Security.<\/strong> A secure lock is not the same as a security-rated assembly. In Europe, RC4 is a burglar resistance class under EN 1627 for a complete assembly. If your project needs a security rating, state which standard and who will approve the evidence.<\/li>\n<\/ul>\n<p>In practice, a standard floor door does not usually carry one test certificate covering fire, load, security and seismic performance together. Where a project combines them, expect a mix of test evidence, assessment and calculation, and agree early who owns each part.<\/p>\n<h2>Specification checklist<\/h2>\n<table class=\"mtr-table mtr-thead-th\">\n<thead>\n<tr>\n<th data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Information to give the manufacturer<\/div><\/th>\n<th data-mtr-content=\"Why it matters\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Why it matters<\/div><\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Clear opening and overall frame size<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Defines the span and whether the tested size covers it<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Fire rating in hours and the criterion<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Integrity only, or integrity and insulation<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Fire direction<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">From below, above or both<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Floor construction and embedded frame<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Whether the slab interface is part of the fire-resisting line<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Uniformly distributed, point, wheel and equipment loads<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">The real load case for the structural engineer<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Operation and controls<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Manual, hydraulic or electric, and any added penetrations<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Security and seismic requirements<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Separate evidence routes<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Information to give the manufacturer\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Who approves the evidence<\/div><\/td>\n<td data-mtr-content=\"Why it matters\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Fire engineer, insurer, code official<\/div><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Frequently asked questions<\/h2>\n<h3>Are Surespan fire rated floor doors UL listed?<\/h3>\n<p>The data sheets do not state a UL listing. The HIAC and SAC sheets name European test standards, BS EN 1634-1: 2008 and BS EN 1363-1: 1999. Ask for the reports and confirm with the code official what evidence is accepted.<\/p>\n<h3>What does &#8220;fire rated from the underside only&#8221; mean?<\/h3>\n<p>That the rating stated on the HIAC and SAC sheets applies to fire exposure from below the floor door. It does not cover fire from above.<\/p>\n<h3>Does &#8220;up to 4 hours&#8221; mean integrity and insulation?<\/h3>\n<p>The HIAC, SAC and EHDC sheets do not say. Integrity and insulation are separate criteria in European fire testing, and a time can refer to one or both, so ask which criterion the hours refer to and get it in writing.<\/p>\n<h3>Can a large bespoke floor door carry the same rating?<\/h3>\n<p>Only if the evidence covers it. For sizes beyond the tested range, ask whether an extended application, classification or expert judgement exists and what it covers.<\/p>\n<p>See the <a href=\"https:\/\/surespancovers.com\/us\/product-category\/floor-hatches\/\">floor hatch range<\/a>. To discuss a fire rated floor door, use the <a href=\"https:\/\/surespancovers.com\/us\/contact-us\/\">Surespan contact page<\/a>.<\/p>\n<h2>Sources<\/h2>\n<ul>\n<li>Surespan data sheet &#8220;Recessed Lid HIAC Floor Door&#8221;, REV 1.0, March 2022: fire rating, standards, loads. Product page: <a href=\"https:\/\/surespancovers.com\/us\/product\/recessed-floor-hatch\/\">Recessed Floor Hatch<\/a>.<\/li>\n<li>Surespan data sheet &#8220;Flush Lid SAC Floor Door&#8221;, REV 1.0, July 2022: fire rating, standards, loads. Product page: <a href=\"https:\/\/surespancovers.com\/us\/product\/flush-floor-hatch\/\">Flush Floor Hatch<\/a>.<\/li>\n<li>Surespan data sheet &#8220;Heavy Duty Floor Door EHDC&#8221;, REV 1.0, July 2022: fire rating. Product page: <a href=\"https:\/\/surespancovers.com\/us\/product\/heavy-duty-floor-hatch\/\">Heavy Duty Floor Hatch<\/a>.<\/li>\n<li>UL 263, Fire Tests of Building Construction and Materials, Edition 14, <a href=\"https:\/\/www.shopulstandards.com\/ProductDetail.aspx?productId=UL263\" target=\"_blank\" rel=\"noopener\">shopulstandards.com<\/a>.<\/li>\n<\/ul>\n","protected":false},"excerpt":{"rendered":"<p>What to ask for when a floor access door sits in a fire-rated floor: test standard, criterion, fire direction, tested size and who accepts the evidence.<\/p>\n","protected":false},"author":2,"featured_media":47726,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"content-type":"","_ayudawp_aiss_exclude":false,"_ayudawp_aiss_exclude_summary":false,"_ayudawp_aiss_summary":"A fire rated floor access door, or fire rated floor hatch, is a floor door built to stop fire passing through an opening in a fire-resistance-rated floor for a stated time. Its rating is only as good as the test evidence behind it: before you accept \"rated up to 4 hours\", ask which standard it was tested to, which performance criterion the time refers to, from which side the fire was applied, and whether the tested size and orientation match your opening. Before a manufacturer can confirm an evidence route, the design team should settle:. whether the requirement is integrity only, or integrity and insulation;. the fire test or classification standard that applies;. the fire exposure direction, from below, from above or both;. whether the tested construction covers the required size;. whether the frame, hinges, seals, insulation and hardware match the tested or assessed construction;. whether the surrounding slab and embedded frame form part of the fire-resisting line;. whether operation, locking, controls or monitoring contacts introduce untested penetrations or changes.","_ayudawp_aiss_summary_provider":"extractive","_ayudawp_aiss_summary_hash":"90063414d4b4869fd70d16da3abd583f1e000e05","footnotes":""},"categories":[525],"tags":[],"country":[],"product-supplied":[],"class_list":["post-50034","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-articles"],"acf":[],"publishpress_future_workflow_manual_trigger":{"enabledWorkflows":[]},"_links":{"self":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts\/50034","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/comments?post=50034"}],"version-history":[{"count":0,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts\/50034\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/media\/47726"}],"wp:attachment":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/media?parent=50034"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/categories?post=50034"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/tags?post=50034"},{"taxonomy":"country","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/country?post=50034"},{"taxonomy":"product-supplied","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/product-supplied?post=50034"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}