{"id":50035,"date":"2026-09-14T08:06:13","date_gmt":"2026-09-14T07:06:13","guid":{"rendered":"https:\/\/surespancovers.com\/us\/floor-access-door-load-ratings\/"},"modified":"2026-09-14T08:06:13","modified_gmt":"2026-09-14T07:06:13","slug":"floor-access-door-load-ratings","status":"publish","type":"post","link":"https:\/\/surespancovers.com\/us\/floor-access-door-load-ratings\/","title":{"rendered":"Floor Access Door Load Ratings: psf, Point Load, Wheel Load and H-20"},"content":{"rendered":"<p>A floor access door load rating can mean four different things: a uniformly distributed load in psf or kN\/m\u00b2 for foot traffic, a point load in pounds or kN from an equipment foot, a wheel load per wheel for carts and vehicles, or H-20, a highway bridge design vehicle borrowed by many US schedules. They are not interchangeable. A door rated for 10\u00a0kN\/m\u00b2 (approx. 209 psf) of foot traffic is not thereby rated for a pallet truck, and no area or wheel figure on a data sheet should be read as an H-20 equivalent.<\/p>\n<p>Whatever the rating, OSHA&#8217;s general industry rule for covers over holes in walking-working surfaces is 29 CFR 1910.29(e): each cover must support, without failure, at least twice the maximum intended load and be secured against accidental displacement. The structural engineer confirms the selection.<\/p>\n<h2>Which load figure applies to your floor door?<\/h2>\n<table class=\"mtr-table mtr-thead-th\">\n<thead>\n<tr>\n<th data-mtr-content=\"If the door will see\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">If the door will see<\/div><\/th>\n<th data-mtr-content=\"Specify\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Specify<\/div><\/th>\n<th data-mtr-content=\"Give it as\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Give it as<\/div><\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td data-mtr-content=\"If the door will see\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Foot traffic and maintenance access<\/div><\/td>\n<td data-mtr-content=\"Specify\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Uniformly distributed load<\/div><\/td>\n<td data-mtr-content=\"Give it as\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">psf or kN\/m\u00b2<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"If the door will see\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Equipment feet, jack legs, outriggers<\/div><\/td>\n<td data-mtr-content=\"Specify\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Point load plus contact area<\/div><\/td>\n<td data-mtr-content=\"Give it as\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">lb or kN, with the footprint<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"If the door will see\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Carts, pallet trucks, forklifts, vehicles<\/div><\/td>\n<td data-mtr-content=\"Specify\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Wheel load plus contact patch and route<\/div><\/td>\n<td data-mtr-content=\"Give it as\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">lb or kN per wheel<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"If the door will see\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Tile, stone or screed set into a recessed lid<\/div><\/td>\n<td data-mtr-content=\"Specify\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Permanent dead load of the infill, plus the imposed load<\/div><\/td>\n<td data-mtr-content=\"Give it as\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">weight and depth of the infill<\/div><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>What does a psf (area load) rating mean?<\/h2>\n<p>A uniformly distributed load, or UDL, is spread over the whole lid and stated per unit area: psf in US practice, kN\/m\u00b2 on European data sheets. Surespan&#8217;s floor door sheets print three pedestrian loads:<\/p>\n<ul>\n<li>pedestrian light, 2.5\u00a0kN\/m\u00b2 (approx. 52 psf);<\/li>\n<li>pedestrian medium, 5\u00a0kN\/m\u00b2 (approx. 104 psf);<\/li>\n<li>pedestrian heavy, 10\u00a0kN\/m\u00b2 (approx. 209 psf).<\/li>\n<\/ul>\n<p>The HIAC recessed, SAC flush and EHDC heavy duty sheets list all three. The RSI upstand door is rated at 2.5 or 5kN\/m2 loading. The floor around the door is designed to a live load from the building code adopted for the project; the door&#8217;s rating is a separate figure, and the engineer checks one against the other.<\/p>\n<p>The warning that matters: a distributed load figure does not approve wheels, jacks, rollers or equipment feet. A UDL assumes the load is spread out. It says nothing about a small, heavy contact.<\/p>\n<h2>What is a point load, and why does it matter more?<\/h2>\n<p>A point load is a concentrated force applied over a small area. On a floor door it comes from an equipment foot, a jack leg, a maintenance stand, a skid plate or a trolley wheel. For floor hatches, point loads often govern the design more than the general imposed load, because a concentrated load can cause local bending, indentation or permanent deflection around a hinge, frame or cover joint. As Surespan&#8217;s guide puts it, a 10\u00a0kN load over 300 \u00d7 300mm (11.8 x 11.8 in) is different from 10\u00a0kN through a small foot.<\/p>\n<p>None of Surespan&#8217;s five floor door sheets prints a point load rating. If your equipment will stand on the lid, give these with the enquiry:<\/p>\n<ul>\n<li>the load value in pounds or kN;<\/li>\n<li>the contact area of each foot or support;<\/li>\n<li>where it can land: center of the lid, edge, hinge side or lock side;<\/li>\n<li>whether it is static or moving, and whether it is dropped or lowered onto the lid;<\/li>\n<li>whether the door must still open after the load has been applied.<\/li>\n<\/ul>\n<h2>How are wheel loads rated?<\/h2>\n<p>A wheel load is the force through one wheel, not the weight of the vehicle. Surespan&#8217;s sheets give vehicle classes as a wheel load in kN:<\/p>\n<table class=\"mtr-table mtr-thead-th\">\n<thead>\n<tr>\n<th data-mtr-content=\"Class as the sheet describes it\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Class as the sheet describes it<\/div><\/th>\n<th data-mtr-content=\"Wheel load printed\" class=\"mtr-th-tag\"><div class=\"mtr-cell-content\">Wheel load printed<\/div><\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td data-mtr-content=\"Class as the sheet describes it\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Car light<\/div><\/td>\n<td data-mtr-content=\"Wheel load printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">W3, 15\u00a0kN wheel load<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Class as the sheet describes it\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Car medium<\/div><\/td>\n<td data-mtr-content=\"Wheel load printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">W4, 25\u00a0kN wheel load<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Class as the sheet describes it\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Car heavy<\/div><\/td>\n<td data-mtr-content=\"Wheel load printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">W5, 50\u00a0kN wheel load<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Class as the sheet describes it\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Van heavy<\/div><\/td>\n<td data-mtr-content=\"Wheel load printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">W6, 65\u00a0kN wheel load<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Class as the sheet describes it\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Heavy goods vehicle<\/div><\/td>\n<td data-mtr-content=\"Wheel load printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">W7, 108\u00a0kN wheel load<\/div><\/td>\n<\/tr>\n<tr>\n<td data-mtr-content=\"Class as the sheet describes it\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">Heaviest class on the sheet<\/div><\/td>\n<td data-mtr-content=\"Wheel load printed\" class=\"mtr-td-tag\"><div class=\"mtr-cell-content\">W8, 158\u00a0kN wheel load<\/div><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>The full table is on the HIAC, SAC and EHDC sheets. Convert your vehicle&#8217;s wheel loads into the same unit before you compare, and give the structural engineer the rest of the picture: number of wheels, axle arrangement, tire type and contact patch, the route across the door, whether a wheel can stop or turn on the lid, and how often traffic crosses. A cart that crosses once a month and a forklift that crosses all day are different design cases.<\/p>\n<h2>What does H-20 mean on a floor door schedule?<\/h2>\n<p>H-20 comes from highway bridge design, not from floor doors. FHWA&#8217;s truck size and weight study lists the H-15, H-20 and HS-20 design vehicles among those most US bridges were designed for, and describes the related HS-20 loading (the &#8220;S&#8221; stands for semitrailer combination) as &#8220;a three-axle semitrailer combination weighing 72,000 pounds with 8,000 pounds on its steering axle and 32,000 pounds on its drive axle and 32,000 pounds on the semitrailer axle.&#8221; When a schedule says &#8220;H-20 rated&#8221;, it is borrowing a bridge loading to say &#8220;trucks will drive over this&#8221;.<\/p>\n<p>Surespan&#8217;s data sheets do not use H-20 or any other US load standard, and none of their figures is an H-20 equivalent. The useful step is to turn the H-20 request back into what the door will actually carry: the heaviest wheel load, its contact area, the speed and how often it crosses. Then the engineer can compare that with a door&#8217;s printed wheel load and confirm it, or ask for a bespoke design.<\/p>\n<h2>What about equipment loads and recessed infill?<\/h2>\n<p>&#8220;Equipment load: 8\u00a0kN&#8221; is not enough on its own. It could be the total weight of a unit, one wheel, one foot or one skid, and the same total weight on four small feet is a far harder case than on a broad baseplate. Ask the equipment supplier for the footprint.<\/p>\n<p>A recessed door adds its own dead load. The HIAC lid can take a recess of up to 100mm (3.9 in), and the sheet says the operation is gas spring on smaller sizes, with larger doors electric or hydraulic &#8220;depending on loading, infill and size.&#8221; State the infill material and depth, because a heavy stone or concrete infill can change the hinges, the gas springs or the need for powered opening.<\/p>\n<h2>Will the door still open after the load?<\/h2>\n<p>Strength is not the only test. A floor door has to stay aligned in its frame. A lid that survives a load but takes a permanent set of a few millimeters can bind, damage its seals or overload its hinges, and then it no longer opens properly. Ask the manufacturer what deflection limit applies and whether the door is designed to remain openable after the stated load. This is also why the support matters: a lid bearing on four sides behaves differently from one bearing on two, and a double-leaf door with a center joint differently again.<\/p>\n<h2>Frequently asked questions<\/h2>\n<h3>What is the difference between psf and a point load?<\/h3>\n<p>A psf rating is a load spread evenly over the lid. A point load is a force through a small contact area, such as an equipment foot. A door can meet a psf rating and still be overloaded by a heavy foot in the wrong place, so give both when equipment will stand on it.<\/p>\n<h3>What is 10\u00a0kN\/m\u00b2 in psf?<\/h3>\n<p>About 209 psf. The sheets&#8217; pedestrian loads of 2.5, 5 and 10\u00a0kN\/m\u00b2 are about 52, 104 and 209 psf.<\/p>\n<h3>Is a 158\u00a0kN wheel load the same as H-20?<\/h3>\n<p>Do not treat it as such. H-20 is a highway bridge design vehicle; the sheet figure is a wheel load class. Compare your actual wheel loads with the sheet, and let the structural engineer decide.<\/p>\n<h3>What load does OSHA require a floor door to carry?<\/h3>\n<p>OSHA sets no load class. Under 29 CFR 1910.29(e), each cover must be capable of supporting, without failure, at least twice the maximum intended load that may be imposed on it at any one time, and must be secured to prevent accidental displacement.<\/p>\n<p>For the doors themselves, see the <a href=\"https:\/\/surespancovers.com\/us\/product-category\/floor-hatches\/\">floor hatch range<\/a>, including the <a href=\"https:\/\/surespancovers.com\/us\/product\/heavy-duty-floor-hatch\/\">heavy duty floor hatch<\/a>, and <a href=\"https:\/\/surespancovers.com\/us\/buy-floor-doors\/\">What is a Floor Door?<\/a> To discuss a load case, send the opening size, support detail and loads through the <a href=\"https:\/\/surespancovers.com\/us\/contact-us\/\">Surespan contact page<\/a>.<\/p>\n<h2>Sources<\/h2>\n<ul>\n<li>Surespan data sheet &#8220;Recessed Lid HIAC Floor Door&#8221;, revision mark REV 1.0 (04\/21), file dated March 2022: load classes, recess, operation. Product page: <a href=\"https:\/\/surespancovers.com\/us\/product\/recessed-floor-hatch\/\">Recessed Floor Hatch<\/a>.<\/li>\n<li>Surespan data sheet &#8220;Flush Lid SAC Floor Door&#8221;, revision mark REV 1.0 (07\/22), July 2022: load classes. Product page: <a href=\"https:\/\/surespancovers.com\/us\/product\/flush-floor-hatch\/\">Flush Floor Hatch<\/a>.<\/li>\n<li>Surespan data sheet &#8220;Heavy Duty Floor Door EHDC&#8221;, revision mark REV 1.0 (07\/22), July 2022: load classes. Product page: <a href=\"https:\/\/surespancovers.com\/us\/product\/heavy-duty-floor-hatch\/\">Heavy Duty Floor Hatch<\/a>.<\/li>\n<li>Surespan data sheet &#8220;Floor Access Hatch RSI Upstand Access Door&#8221;, revision mark REV 1.0 (07\/22), July 2022: load rating. Product page: <a href=\"https:\/\/surespancovers.com\/us\/product\/upstand-floor-hatch\/\">Upstand Floor Hatch<\/a>.<\/li>\n<li>OSHA 29 CFR 1910.29, paragraph (e), <a href=\"https:\/\/www.osha.gov\/laws-regs\/regulations\/standardnumber\/1910\/1910.29\" target=\"_blank\" rel=\"noopener\">osha.gov<\/a>.<\/li>\n<li>FHWA, Comprehensive Truck Size and Weight Study, Volume 3, Chapter 6 (bridge design vehicles), fhwa.dot.gov.<\/li>\n<\/ul>\n","protected":false},"excerpt":{"rendered":"<p>Why 10\u00a0kN\/m\u00b2 (approx. 209 psf) is not a wheel load, what H-20 means on a floor door schedule, and the load information a manufacturer needs.<\/p>\n","protected":false},"author":2,"featured_media":47989,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"content-type":"","_ayudawp_aiss_exclude":false,"_ayudawp_aiss_exclude_summary":false,"_ayudawp_aiss_summary":"A floor access door load rating can mean four different things: a uniformly distributed load in psf or kN\/m\u00b2 for foot traffic, a point load in pounds or kN from an equipment foot, a wheel load per wheel for carts and vehicles, or H-20, a highway bridge design vehicle borrowed by many US schedules. For floor hatches, point loads often govern the design more than the general imposed load, because a concentrated load can cause local bending, indentation or permanent deflection around a hinge, frame or cover joint. If your equipment will stand on the lid, give these with the enquiry:. the load value in pounds or kN;. the contact area of each foot or support;. where it can land: center of the lid, edge, hinge side or lock side;. whether it is static or moving, and whether it is dropped or lowered onto the lid;. whether the door must still open after the load has been applied.","_ayudawp_aiss_summary_provider":"extractive","_ayudawp_aiss_summary_hash":"7fce21d610cf74990f95e3ecd875e7d76e9aa8f4","footnotes":""},"categories":[525],"tags":[],"country":[],"product-supplied":[],"class_list":["post-50035","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-articles"],"acf":[],"publishpress_future_workflow_manual_trigger":{"enabledWorkflows":[]},"_links":{"self":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts\/50035","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/comments?post=50035"}],"version-history":[{"count":0,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/posts\/50035\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/media\/47989"}],"wp:attachment":[{"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/media?parent=50035"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/categories?post=50035"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/tags?post=50035"},{"taxonomy":"country","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/country?post=50035"},{"taxonomy":"product-supplied","embeddable":true,"href":"https:\/\/surespancovers.com\/us\/wp-json\/wp\/v2\/product-supplied?post=50035"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}