Roof Hatch and Smoke Vent in One: How Combined Units Work

Can one roof hatch also be a smoke vent? The two ways to do it, a single lid or two leaves in one frame, with sizes and what to check on a US project.

Yes, one roof opening can give roof access and also vent smoke, but only when the unit is built and tested as a smoke vent. A standard roof hatch is not a smoke vent. Surespan offers two ways to do both jobs: a smoke vent whose lid also opens for daily access and ventilation (the smoke vent with access, SRH-PAOV), and an Exi-Vent, which puts a roof access hatch and a smoke vent side by side in one unit, split by a rain gutter. Both are CE marked to EN 12101-2, the European smoke vent standard. In the US the product standard for automatically operated roof vents is UL 793, and Surespan’s data sheets do not claim a UL 793 listing.

Why is a standard roof hatch not a smoke vent?

A smoke vent has to open automatically on a fire signal and deliver a tested airflow area. A standard roof hatch is built for people to pass through, and its data sheet gives no EN 12101-2 smoke vent evidence, so do not count it as smoke venting. Where one opening must do both, choose a product made for both.

Option 1: a smoke vent with access

The smoke vent with access (SRH-PAOV) is a single insulated lid that is the smoke vent and also opens for people. Its data sheet lists:

  • Use: thermally broken, with daily ventilation and access; CE Marked to EN12101-2.
  • Operation: a 24V DC/4A actuator, with a 24V control center, fireman’s switch, key switch, push button and smoke detector. An offset actuator for roof access is offered free of charge. The drawing shows the lid opening to 140°.
  • Curb: 300mm (11.8 in) in height with external curb liner, thermal break and 50mm polyisocyanurate insulation to 0.43 W/m²K. That is the U-value of the insulation, not of the whole unit. Non-combustible mineral wool insulation is also available free of charge.
  • Sizes: up to 1260 x 1260 mm (49.6 x 49.6 in), with bespoke sizes available; can be installed up to 15° pitch; aluminum wind deflectors.
  • Ladders and accessories: arrangements with a ZIP retractable ladder or a vertical ladder, plus a ladder safety post, fixed handhold and Sureguard handrail.

The older 2018 sheet for the SRHP/AOV solid lid vent describes the same idea as a “Thermally Broken Solid top Smoke Vent with roof access and comfort ventilation”, and lists an 800 x 1260 For Personnel Access opening (approx. 31.5 x 49.6 in) and an offset mechanism as options.

Option 2: an access hatch and a smoke vent in one frame

The Exi-Vent roof hatch (SV-EXI) uses two leaves instead of one. The sheet says the hatch and smoke vent are split by a minimum 150mm (5.9 in) rain gutter, and gives three examples:

Overall
Roof access hatch
Smoke vent
4700 x 1300 mm (185.0 x 51.2 in)
3460 x 1300 mm (136.2 x 51.2 in)
1300 x 1050mm (51.2 x 41.3 in)
5000 x 1200 mm (196.9 x 47.2 in)
3590 x 1200 mm (141.3 x 47.2 in)
1200 x 1200 mm (47.2 x 47.2 in)
3800 x 1260 mm (149.6 x 49.6 in)
2600 x 1260 mm (102.4 x 49.6 in)
1260 x 1000 mm (49.6 x 39.4 in)

For the first example the sheet adds: “The units can be operated independently.” Confirm that for the configuration you specify. The Exi-Vent is made to any size, can be installed up to 30° pitch, and is CE marked to EN12101-2. Its ladder arrangements include a ZIP ladder, a vertical ladder and a companionway ladder, which suits a larger access opening over a ship’s ladder.

Which one should you choose?

Question
Smoke vent with access (SRH-PAOV)
Exi-Vent (SV-EXI)
How many leaves?
One lid does both jobs
A separate access hatch and smoke vent
Size
Up to 1260 x 1260 mm, bespoke sizes available
Made to any size
Roof pitch
Up to 15°
Up to 30°
Ladder arrangements on the sheet
ZIP or vertical ladder
ZIP, vertical or companionway ladder

The honest limit of a single-lid unit is that the vent and the access door are the same leaf: whatever is stored or fitted around the opening for access must never stop the lid opening on alarm. Where the access opening needs to be large, or the two functions should be kept apart, the twin-leaf Exi-Vent is the cleaner answer.

What should you check on a US project?

  1. Listing. UL 793, Automatically Operated Roof Vents for Smoke and Heat, is the US product standard. If your project or authority having jurisdiction requires a UL 793 listed vent, settle that first: Surespan’s evidence is testing and CE marking to EN 12101-2.
  2. Area. Ask for the aerodynamic area of the exact size and model and confirm which area your engineer’s method uses.
  3. Controls. Specify the fire alarm interface, the control center, the fireman’s switch and the daily ventilation controls together, so access use cannot override the smoke function.
  4. Ladder at the hatch. Where employees use a fixed ladder that ends at the hatch, OSHA 29 CFR 1910.23(d)(9) requires the hatch cover to open “with sufficient clearance to provide easy access to or from the ladder.”
  5. Edge protection. An open roof hatch is a hole in the roof. Plan the guardrail with the safety professional; the Sureguard handrail is listed as an accessory.

Frequently asked questions

Can a roof hatch be used as a smoke vent?

Not a standard roof hatch. Use a unit that is tested as a smoke vent and also gives access, such as a smoke vent with access or an Exi-Vent.

Can the smoke vent with access be opened every day?

Yes. The SRH-PAOV sheet lists daily ventilation and access as features. Daily use does not change the need to keep the lid free to open on alarm.

Do the two leaves of an Exi-Vent open separately?

The sheet says so for one of its examples: the units can be operated independently. Confirm it for your configuration.

Are these units UL listed?

The data sheets do not state a UL listing. They state CE marking to EN 12101-2. Agree the acceptable evidence with the authority having jurisdiction.

See the full smoke vent range and the roof hatch range. To discuss a combined opening, send the roof build-up, the access route and the vent area required through the Surespan contact page.

Sources

  • Surespan data sheet “Thermally Broken AOV” (SRH-PAOV), revision mark REV 1.0 (06/22), June 2022: features, operation, controls, curb, insulation, sizes, pitch, options, ladder arrangements. Product page: Smoke Vent with Access.
  • Surespan data sheet “Exi-Vent” (SV-EXI), revision mark REV 1.0 (06/22), June 2022: layout, gutter, examples, sizes, pitch, CE marking, ladder arrangements. Product page: Exi-Vent Roof Hatch.
  • Surespan data sheet “Smoke Vent SRHPAOV” (SRHP/AOV), RF REV 3 05/18, May 2018: description, personnel access, options. Range: Smoke Vents.
  • UL 793, Automatically Operated Roof Vents for Smoke and Heat, Edition 4, shopulstandards.com.
  • OSHA 29 CFR 1910.23 (ladders), paragraph (d)(9), osha.gov.