Ladder Cages and the OSHA 24-Foot Rule: What Changes by 2036

When OSHA still accepts a ladder cage on a fixed ladder over 24 feet, what new and replaced ladders need, and what changes on November 18, 2036.

Under OSHA’s general industry rule 29 CFR 1910.28(b)(9), a fixed ladder that extends more than 24 feet (7.3 m) above a lower level must have fall protection. A ladder installed before November 19, 2018 may still rely on a cage or well, but a ladder installed on or after that date needs a personal fall arrest system or a ladder safety system, and on and after November 18, 2036 every such fixed ladder must have one of those two. A cage on its own will no longer count.

This article covers the federal OSHA rule in 29 CFR 1910, subpart D, which applies to all general industry workplaces (1910.21(a)). Building codes and other rules that apply to your project can add their own requirements.

What does OSHA 1910.28(b)(9) say?

For fixed ladders that extend more than 24 feet (7.3 m) above a lower level, the employer must ensure:

Ladder
What it must be equipped with
Paragraph
Installed before November 19, 2018
A personal fall arrest system, ladder safety system, cage, or well
(b)(9)(i)(A)
Installed on and after November 19, 2018
A personal fall arrest system or a ladder safety system
(b)(9)(i)(B)
Ladder, cage or well, or a portion of a section, replaced
A personal fall arrest system or ladder safety system, in at least the section where the replacement is located
(b)(9)(i)(C)
All fixed ladders, on and after November 18, 2036
A personal fall arrest system or a ladder safety system
(b)(9)(i)(D)

Two more paragraphs set the layout. Where a ladder has a personal fall arrest system or ladder safety system, the system must protect the climber throughout the entire vertical distance of the ladder, including all ladder sections, and the ladder must have rest platforms at maximum intervals of 150 feet (45.7 m), (b)(9)(ii). Ladder sections that have a cage or well must be offset from adjacent sections and have landing platforms at maximum intervals of 50 feet (15.2 m), (b)(9)(iii).

Why does a cage no longer count as fall protection?

OSHA’s definitions answer this directly. A ladder safety system “means a system designed to eliminate or reduce the possibility of falling from a ladder”, usually a carrier, safety sleeve, lanyard, connectors and body harness, and the definition ends: “Cages and wells are not ladder safety systems.” A cage is an enclosure around the climbing space, designed to contain a climber in a fall and direct them to a lower landing (1910.29(g)(3)). It is not a ladder safety system.

So a cage installed today on a ladder over 24 feet does not meet (b)(9) on its own. It can still be fitted, but the ladder also needs a ladder safety system or personal fall arrest system.

What do cages and ladder safety systems have to meet?

OSHA 29 CFR 1910.29 sets the criteria. For cages, wells and platforms, 1910.29(g):

  • cages and wells permit easy access to, and egress from, the ladder they enclose;
  • cages and wells are continuous throughout the length of the fixed ladder, except for access, egress and other transfer points;
  • cages and wells are designed, constructed and maintained to contain employees in the event of a fall and to direct them to a lower landing;
  • platforms used with fixed ladders provide a horizontal surface of at least 24 inches by 30 inches (61 cm by 76 cm).

For ladder safety systems, 1910.29(i):

  • the system allows the employee to climb up and down using both hands and does not require the employee to continuously hold, push or pull any part of the system while climbing;
  • the connection between the carrier or lifeline and the point of attachment to the body harness or belt does not exceed 9 inches (23 cm);
  • mountings for rigid carriers are attached at each end, with intermediate mountings as needed along the entire length;
  • flexible carriers have cable guides installed at least 25 feet (7.6 m) apart but not more than 40 feet (12.2 m) apart.

What should you do with an existing caged ladder?

  1. Measure the climb. The 24-foot trigger is the distance the ladder extends above a lower level, not the length of one section.
  2. Find the installation date. A ladder installed before November 19, 2018 may keep its cage or well for now. One installed on or after that date needs a ladder safety system or personal fall arrest system already.
  3. Watch replacements. If any section of the ladder, cage or well is replaced, that section needs a ladder safety system or personal fall arrest system.
  4. Plan for November 18, 2036. By then every fixed ladder over 24 feet needs one of the two systems, whatever its age.
  5. Check platforms. Rest platforms at maximum intervals of 150 feet with a ladder safety system; offset sections and landings at maximum intervals of 50 feet where a cage or well is the protection.

Where does a short roof access ladder fit in?

Many roof access ladders are well under 24 feet. Where an internal fixed ladder from the top floor up through a roof hatch extends no more than 24 feet above the lower level, (b)(9) does not apply to it, though the fixed ladder rules of 1910.23 do. Moving the access point inside the building is one way to avoid a long external climb altogether. See the roof hatch range for hatches that pair with a fixed ladder.

What does Surespan’s fixed ladder sheet offer?

Surespan’s standard fixed vertical ladder (SL) data sheet lists a caged version, SLC, with standard cages for ladders over 2.5 m (approx. 8.2 ft) high or optional mesh lined cages, and a padlock security closure. The cage is made from 50 x 5 mm flat hoops at a maximum of 900 mm (approx. 35.4 in) on center, with 6 vertical straps, and the stays are at a maximum of 2400 mm (approx. 94.5 in) on center. The sheet also lists a ladder guard, landing platforms, a security closure and a retractable handhold as options, and recommends Surespan landing platforms at 6 m (approx. 19.7 ft) between platforms or landings.

Read those figures as product details, not as an OSHA answer. A Surespan cage is not a ladder safety system or a personal fall arrest system, and on a fixed ladder that extends more than 24 feet it does not by itself provide the fall protection (b)(9) requires. Specify the ladder safety system or personal fall arrest system separately for those ladders, and have the arrangement checked by your safety professional. See the access ladder range for the other ladder types.

Frequently asked questions

Are ladder cages illegal under OSHA?

No. Cages may still be installed and are still covered by 1910.29(g). What changed is that a cage alone no longer satisfies the fall protection duty for new fixed ladders over 24 feet, and from November 18, 2036 it no longer satisfies it for any fixed ladder over 24 feet.

Who can work on a fixed ladder that extends more than 24 feet?

OSHA does not answer this by naming a type of worker. 1910.28(b)(9) puts the duty on the employer: the ladder must be equipped as the table above sets out, depending on when it was installed, and from November 18, 2036 every such ladder must have a personal fall arrest system or a ladder safety system.

Does OSHA require a cage on a fixed ladder?

Not for ladders installed on or after November 19, 2018. For those, the required protection over 24 feet is a personal fall arrest system or a ladder safety system.

What is the 2036 deadline?

Under 1910.28(b)(9)(i)(D), on and after November 18, 2036, all fixed ladders that extend more than 24 feet above a lower level are equipped with a personal fall arrest system or a ladder safety system.

How far apart must platforms be?

At maximum intervals of 150 feet (45.7 m) for rest platforms on a ladder with a ladder safety system or personal fall arrest system, and at maximum intervals of 50 feet (15.2 m) for landing platforms on caged or well sections, which must also be offset.

To talk through a fixed ladder for a roof or plant area, send the climb height and the access arrangement through the Surespan contact page. Drawings are in the ladder resources.

Sources

  • Surespan data sheet “Standard Ladder Access SL”, undated: SLC cage, hoops, straps, stays, options, landing platform recommendation. Product page: Fixed Vertical Ladders.
  • OSHA 29 CFR 1910.28 (duty to have fall protection), paragraph (b)(9), osha.gov.
  • OSHA 29 CFR 1910.29 (fall protection systems criteria), paragraphs (g) and (i), osha.gov.
  • OSHA 29 CFR 1910.21 (scope and definitions), osha.gov.