A recessed floor access door, also called a recessed floor hatch or tile-in floor door, is a framed hatch set into a floor opening with a lid shaped as a tray, so the lid can be filled with the same tile, stone, concrete or other finish as the floor around it. To specify one you state six things: the load it must carry, the structural and clear openings, the infill and its depth, how water is handled, how it opens, and whether it needs a fire rating. On a US workplace floor, OSHA 29 CFR 1910.29(e) also asks that a cover over a hole supports at least twice the maximum intended load and is secured against accidental displacement.
For what a floor door is and where it is used, see What is a Floor Door?. This guide is about the recessed, infilled type: Surespan’s Recessed Floor Hatch (HIAC).
What load does the floor door have to carry?
Start with the load, not the word “drive-over”. A cover for a trolley is not a cover for a forklift or a truck wheel. Define the traffic (pedestrian, trolleys, forklift, truck, accidental over-run), and remember the design is checked against the worst wheel position: an edge, a corner or the hinge line.
The HIAC data sheet lists the loads below. The wheel loads are printed with a class code; the pedestrian loads are given as uniformly distributed loads.
Use |
Load on the HIAC sheet |
|---|---|
Pedestrian, light |
2.5 kN/m² (approx. 52 psf) |
Pedestrian, medium |
5 kN/m² (approx. 104 psf) |
Pedestrian, heavy |
10 kN/m² (approx. 209 psf) |
Car, light |
W3, 15 kN wheel load |
Car, medium |
W4, 25 kN wheel load |
Car, heavy |
W5, 50 kN wheel load |
Van, heavy |
W6, 65 kN wheel load |
Truck, heavy |
W7, 108 kN wheel load |
Heaviest class on the sheet |
W8, 158 kN wheel load |
US project teams usually state a live load in psf or a design vehicle, and those do not map one to one onto the classes above. Give the actual wheel or axle load and how often it occurs, set it beside the value the sheet states, and let the structural engineer decide. Surespan’s guidance is that fabricated covers are typically limited to slow-moving off-street traffic, under 20 mph.
Structural opening or clear opening?
- Structural opening: the opening in the slab that the frame is built to fit, close to what US framers call the rough opening.
- Clear opening: the usable space once the frame, hinges, supports and lid are in.
They are rarely the same. If something has to pass through, such as a pump, a valve or a cable drum, state the clear opening it needs before the hatch is sized. The HIAC is custom made to any size.
What can go in the lid, and how deep?
The HIAC lid is a recess that accepts any type of infill: tile, stone, pavers, concrete, plywood, wood or laminate. The sheet gives a maximum recess depth for the infill of up to 100mm (3.9 in). Coordinate these before you fix the floor level:
- the infill material and its thickness;
- the bedding layer and the edge detail;
- the recess depth and the finished floor level;
- tolerances;
- the load case with the infill in place, because infill adds weight to a lid that people have to lift.
The underside of the lid is clad and the top trim is polished stainless steel. The frame is extruded aluminum or fabricated stainless steel, and the standard material depends on size: aluminum, stainless steel grade 304 or grade 316. A SureGrip non-slip finish is available.
Is a recessed floor door watertight?
Not by default. The HIAC uses double EPDM seals and a double unbroken seal to the lid, but Surespan’s guidance is that standard fabricated access covers are designed to be self-draining, not pressure-watertight: water that passes the seals is channelled to a drainage connection. Decide the water strategy early: managed ingress, self-draining, sealed and drained, or a true watertight requirement. If the chamber below must resist standing water pressure, say so in the specification, because it needs a different, bolted and gasketed design.
How does it open, and how is it held open?
A tiled lid is heavy, so opening is a safety decision. On the HIAC sheet, smaller sizes use a gas spring and larger ones use electric or hydraulic operation, depending on the loading, the infill and the size.
- Manual: lock LO1, a hold open stay, operated with a T key from above and operable from both sides. The drawing shows an opening angle of 85.0°.
- Electric: two 24V actuators with brackets backed up to the structure; the actuators lock in position, and the control panel has 72 Hour battery back up.
- Hydraulic: hydraulic actuators with a manual hand pump or electric drive, and options for alarms and contact sensors.
Other locking options on the sheet include an LO3 Tee lock, a locking box, a shoot bolt, a cam lock and a concealed deadlock. In public areas, decide who may open it and whether it needs a release from below. While the door is open, the hole needs protecting: on a workplace floor, OSHA 29 CFR 1910.28(b)(3)(i) asks for covers, guardrail systems, travel restraint or personal fall arrest where the hole is 4 feet or more above a lower level.
Can a recessed floor door be fire rated?
The HIAC sheet gives a fire rating from the underside only, up to 4 hours, tested to BS EN 1634-1: 2008 and BS EN 1363-1: 1999. These are European tests. The sheet does not name the criterion the hours apply to, and it states no rating from above. Ask for the test or classification report, the criterion, the fire direction and the tested size, and agree with the authority having jurisdiction what evidence it accepts for a rated floor. The sheet also gives an acoustic rating of up to 45dB.
Is a recessed hatch the right type?
Choose the recessed, infilled lid where the floor finish must run across the door. Where appearance matters less, a plain metal lid is simpler and lighter: the Flush Floor Hatch has a flush metal lid, and the Heavy Duty Floor Hatch is for demanding industrial areas. See the full floor hatch range.
What to send for a quote
- Application and location: plant room, valve pit, sump, depot, internal floor or external slab.
- Traffic and the worst credible load: wheel or axle load, frequency, turning, braking or parking on the cover.
- Structural opening and clear opening, with what has to pass through.
- Infill material, thickness, bedding, edge detail and finished floor level.
- Water strategy and the corrosion environment.
- Operation: manual, gas spring, electric or hydraulic, with hold-open, locking and release from below.
- Fire rating, if the floor is rated, and the evidence your authority having jurisdiction needs.
Frequently asked questions
Can I put tile or stone in a floor access door?
Yes, in a recessed lid. The HIAC accepts any type of infill to a recess depth of up to 100mm (3.9 in). Coordinate the infill weight, bedding and edge detail with the load case.
Can vehicles drive over a recessed floor hatch?
Yes, if it is made for that load. The HIAC sheet lists wheel loads from W3, 15 kN to W8, 158 kN. State the real vehicle and wheel load rather than “drive-over”.
What does OSHA require of a floor hatch cover?
Under 29 CFR 1910.29(e), each cover for a hole in a walking-working surface is capable of supporting without failure at least twice the maximum intended load, and is secured to prevent accidental displacement.
Does a floor door need a drain?
Often, where it is outdoors. Decide whether water is allowed in and drained, or kept out, and detail the drainage connection.
Data sheets and drawings are in the floor hatch resources. To ask about a specification, use the Surespan contact page.
Sources
- Surespan data sheet “Recessed Lid HIAC Floor Door”, REV 1.0, April 2021 (file dated March 2022): lid, materials, recess depth, loads, seals, operation, locking, fire and acoustic ratings. Product page: Recessed Floor Hatch.
- OSHA 29 CFR 1910.29(e), covers, osha.gov, and 29 CFR 1910.28(b)(3), holes, osha.gov.