No single US rule covers a roof hatch. In a workplace, OSHA’s general industry rules (29 CFR 1910) set how workers are protected from falling through a hatchway and what a fixed ladder up to the hatch must look like. The International Mechanical Code (IMC) sets when rooftop equipment needs permanent access and when a hatch near a roof edge needs a guard. The International Building Code (IBC), as adopted by your state or city, sets roof access and the size of the opening.
This guide sets out what each one asks, with the paragraph to check, and then turns it into a specification checklist. Codes are adopted and amended locally: always confirm the edition and amendments that apply to your project.
What does OSHA require at a roof hatch?
Protection at the hatchway
Under 29 CFR 1910.28(b)(3)(v), each employee is protected from falling through a hatchway and chute-floor hole by one of three arrangements:
- a hinged floor-hole cover that meets the criteria in 1910.29 and a fixed guardrail system that leaves only one exposed side, with the cover closed or a removable guardrail on the exposed sides when the hole is not in use;
- a removable guardrail system and toeboards on not more than two sides of the hole and a fixed guardrail system on all other exposed sides;
- a guardrail system or a travel restraint system when a work operation needs material to be passed through the hatchway.
Where guardrails are used around holes that serve as points of access, such as ladderways, the opening has a self-closing gate that slides or swings away from the hole, or is offset so that no one can walk or fall into the hole, 1910.29(b)(13). The top rail is 42 inches (107 cm), plus or minus 3 inches (8 cm), above the walking-working surface, 1910.29(b)(1), and withstands a force of at least 200 pounds (890 N), 1910.29(b)(3). A cover for a hole supports at least twice the maximum intended load and is secured to prevent accidental displacement, 1910.29(e).
The fixed ladder up to the hatch
OSHA 29 CFR 1910.23 covers the ladder. The figures most often asked about for a hatch ladder:
Item |
OSHA text |
Paragraph |
|---|---|---|
Rung spacing |
not less than 10 inches (25 cm) and not more than 14 inches (36 cm) apart |
1910.23(b)(2) |
Clear width of rungs |
16 inches (41 cm) for fixed ladders, measured before installation of ladder safety systems |
1910.23(b)(4) |
Space behind the ladder |
7 inches (18 cm) minimum from the centerline of the rungs to the nearest permanent object in back of the ladder |
1910.23(d)(2) |
Grab bars |
extend 42 inches (1.1 m) above the access level or landing platforms served by the ladder |
1910.23(d)(7) |
Side rails of through or side-step ladders |
extend at least 42 inches (1.1 m) above the top of the access level or landing platform |
1910.23(d)(4) |
Hatch cover where a fixed ladder ends at a hatch |
opens with sufficient clearance to provide easy access to or from the ladder, and opens at least 70 degrees from horizontal if the hatch is counterbalanced |
1910.23(d)(9) |
If the ladder extends more than 24 feet (7.3 m) above a lower level, 1910.28(b)(9) adds fall protection on the ladder itself.
What does the IMC require?
ICC’s CodeNotes on the 2021 International Mechanical Code describes two sections that touch roof hatches:
- IMC 306.5, access to equipment on roofs: portable ladders are permitted where the vertical distance that must be climbed is not more than 16 feet above grade. For climbs exceeding 16 feet, a permanent fixed ladder attached to the building or some other approved permanent means of access is required. The access shall not require climbing over obstructions greater than 30 inches (762 mm) in height.
- IMC 304.11, guards: guards are to be provided where components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof edge or open side of a walkway, and that edge is more than 30 inches (762 mm) above the floor, roof or grade below. The guard extends not less than 30 inches (762 mm) beyond each end of the roof hatch parallel to the roof edge, its top is not less than 42 inches (1067 mm) above the adjacent elevated surface, and it prevents the passage of a 21-inch diameter (533 mm) sphere. An exception allows anchorage connector devices for fall arrest in place of guards.
What does the IBC require?
In the IBC, roof access is dealt with in section 1011.12. This guide does not quote the model code text; one official state interpretation shows how it is applied. North Carolina’s Office of State Fire Marshal, in an answer dated September 12, 2018 on the 2018 North Carolina Building Code, describes section 1011.12.2 as one “which requires a 16 square foot opening”. In the same answer it sends roof access openings in buildings of three stories or less to section 306.3 of the North Carolina Mechanical Code: an opening of 20 x 30 inches, or large enough for the largest mechanical equipment to pass through, whichever is larger.
That shows how much the answer depends on the state, and on the edition: the answer was given under the 2018 North Carolina code. Check section 1011.12 in the edition your jurisdiction has in force, its exceptions and any state amendment, before you fix the hatch size.
How do you turn the rules into a specification?
Decision |
What to settle |
|---|---|
Purpose |
Maintenance access, equipment transfer or occasional inspection. This sets size and frequency of use. |
Size |
The opening the adopted code requires, and the largest item that must pass through. Standard sizes on Surespan’s SLHP sheet run from 600 x 600 mm (23.6 x 23.6 in) to 1200 x 1200 mm (47.2 x 47.2 in). Where the code or the equipment needs more, bespoke sizes are available. |
Location |
Distance to the roof edge (IMC 304.11 guard), wind exposure and snow load. |
Ladder |
Fixed vertical, retractable or companionway (ship’s) ladder, with the OSHA 1910.23 figures above checked on the ladder drawing. |
Fall protection |
One of the arrangements in 1910.28(b)(3)(v). Where a guardrail is used around the hatch as a point of access, its opening has a self-closing gate or is offset, 1910.29(b)(13). |
Opening |
Gas spring, electric or sliding. A hold-open stay so the cover cannot close on the user. |
Locking |
Padlockable (LO4), European deadlock with thumb turn and key (LO6) or key both sides (LO7). |
Insulation |
Polyiso (PIR) for lower heat loss, or non-combustible mineral wool. |
Fire |
A fire rated hatch where the roof is part of a rated assembly. |
Which Surespan roof hatch fits which case?
- Standard roof hatch: hinged, for pedestrian access with standard sizes.
- Sliding roof hatch (SLHP): a sliding cover for tight or windy locations. Its sheet gives a 220 mm (8.7 in) curb, 50 mm polyiso insulation to 0.43 W/m²K (the U-value of the insulation, not of the whole hatch) and manual or electric opening.
- Double leaf roof hatch (SRHP/DL): two leaves for larger openings, with a 300 mm (11.8 in) curb and gas spring assisted opening.
- Fire rated roof hatch (SRHTB/FR): integrity for 60/90/120/240 minutes, test standard EN1634-1:2014 as printed on its drawings. The sheet states integrity only: ask for the classification report, the fire direction and the tested size.
One limit to be clear about: a data sheet tells you what the product is. Whether the arrangement on your roof meets OSHA, the IMC and your adopted building code is decided by the design team and the code official, from the drawings of the whole access route.
Frequently asked questions
Where does the minimum roof hatch size come from?
The OSHA paragraphs quoted in this guide set how the hatchway is protected, 1910.28(b)(3)(v), and how a hatch cover at the top of a fixed ladder opens, 1910.23(d)(9). For the size of the opening, look to the building and mechanical codes your jurisdiction adopted.
Does a roof hatch need a guardrail?
For workers, OSHA 1910.28(b)(3)(v) requires one of the protections listed above at a hatchway. Under the 2021 IMC as described by ICC, a guard is required where a roof hatch opening is within 10 feet of a roof edge that is more than 30 inches above the level below.
How far must ladder rails extend above a roof hatch?
OSHA 1910.23(d)(7) has grab bars extend 42 inches above the access level, and 1910.23(d)(4) has the side rails of through or side-step ladders extend at least 42 inches above the access level. ICC’s CodeNotes on IMC 306.5 describes side rails extending at least 30 inches above the parapet or roof surface. Where both apply, design to the stricter figure.
When does rooftop equipment need a permanent ladder?
Under IMC 306.5 as described by ICC, when the climb exceeds 16 feet above grade.
Related reading: How to choose the right roof hatch and A roof hatch is not just a square box. For a specification for your project, use the Surespan contact page.
Sources
- Surespan data sheet “Thermally Broken SLHP (Telescopic) Sliding Hatch”, REV 2.0, March 2022. Product page: Sliding Roof Hatch.
- Surespan data sheet “Double Door Roof Hatch SRHP/DL”, July 2022. Product page: Double Leaf Roof Hatch.
- Surespan data sheet “Fire Rated Roof Hatch” (SRHTB/FR), March 2026 (revision mark 06/22). Product page: Fire Rated Roof Hatch.
- OSHA 29 CFR 1910.23, 1910.28 and 1910.29, 1910.23, 1910.28, 1910.29 on osha.gov.
- ICC, CodeNotes: Worker Safety on Roofs and Elevated Surfaces (2021 IMC 304.11 and 306.5), iccsafe.org.
- NC Office of State Fire Marshal, interpretation 1011.12.2, Roof Access Opening for 3-Story or Less Building (2018 NC Building Code, September 12, 2018), ncosfm.gov.