UL 793, NFPA 204 and EN 12101-2: Smoke Vent Standards Compared

What UL 793, NFPA 204 and EN 12101-2 each cover, why a CE marked smoke vent is not a UL listed one, and what to ask for on a US project.

UL 793 and EN 12101-2 are both product standards for roof smoke vents: UL 793, Automatically Operated Roof Vents for Smoke and Heat, is the American one, and EN 12101-2 is the European one that Surespan’s smoke vents are tested and CE marked to. NFPA 204, Standard for Smoke and Heat Venting, is the design standard for venting itself. Evidence under one standard does not carry over to another: a vent CE marked to EN 12101-2 is not thereby UL 793 listed, and the authority having jurisdiction decides what it accepts.

This guide is for US design teams who receive a European smoke vent data sheet and need to judge what it does and does not prove. Building and fire code triggers for vents are outside its scope.

What does each standard cover?

Standard
What it is
What it covers
UL 793, Automatically Operated Roof Vents for Smoke and Heat (Edition 4, published December 15, 2020, last revised July 30, 2026)
US product standard
Automatically operated roof vents for smoke and heat in two general categories, mechanically-opened and gravity-opened, operated manually or automatically in a fire to remove smoke and heat from the building.
NFPA 204, Standard for Smoke and Heat Venting
US design standard
Smoke and heat venting, as its title says: how venting is designed for a building, not how one product is tested.
EN 12101-2
European product standard for natural smoke and heat exhaust ventilators
Test methods and classifications for opening reliability, aerodynamic free area, wind and snow resistance, low-temperature operation, heat exposure and corrosion. Conforming products carry a Declaration of Performance and can be CE marked under the Construction Products Regulation.

Two of the three test a product; NFPA 204 is the design standard. A product standard says how one vent performed in a test; it does not say how many vents a building needs or where they go.

What is the key difference between UL 793 and EN 12101-2?

Read the UL 793 scope closely. It describes mechanically-opened vents as “a body frame, one or more damper covers and hatches, and operating mechanisms which generally include a heat responsive device and spring(s)”, and gravity-opened vents as “a body frame and nonmetallic drop-out panel.” It then says: “Automatic operation does not depend on electrical power or other energy sources that may be interrupted during a fire”. Instead, it depends on a heat responsive device, or on a plastic cover shrinking and falling from place due to fire exposure, “or the like.”

Surespan’s EN 12101-2 vents open differently. The smoke vent with access (SRH-PAOV) sheet lists a 24V DC/4A actuator and these controls: a 24V control center, a fireman’s switch, a key switch, a push button and a smoke detector. The 2018 sheet for the SRHP/AOV solid lid vent lists a 24VDC control panel with 72 hour battery backup. These are actuator-driven vents, opened by power from a control panel.

Read the UL 793 scope sentence against the operating method of any vent you compare. Whether a particular vent design can be evaluated under UL 793 is a question for UL and the manufacturer. A data sheet does not answer it.

What EN 12101-2 evidence does a Surespan data sheet show?

Three kinds, depending on the sheet:

  • CE marking. The smoke vent with access (SRH-PAOV) and the custom smoke vent (SRH-AOV) sheets state CE Marked to EN12101-2.
  • Classes. The 2018 SRHP/AOV sheet prints its EN12101-2 classes: snow load SL500, low ambient temperature T (-15°), wind load WL1500 and resistance to heat B300. It adds that these apply to the SRHP/AOV only and that other models may differ.
  • Areas. The SRH-AOV sheet gives a geometric area without wind deflectors and an aerodynamic area to EN12101-2 with wind deflectors. For the SRH-AOV/200.120, at 2000 x 1200 mm (78.7 x 47.2 in), those are 2.40m² and 1.58m².

When you compare a European vent with a US one, compare like with like: the same property, the same model and the same size. Ask for the Declaration of Performance and the test report for the exact model and size, not a range brochure.

How should a US project handle a European smoke vent?

  1. Settle the requirement first. Ask the fire protection engineer and the authority having jurisdiction whether the project needs listed vents, and to which standard.
  2. If UL 793 listing is required, say so on the schedule. EN 12101-2 test evidence and CE marking are not a UL 793 listing. Surespan’s data sheets do not claim one, so if the requirement is a UL 793 listed vent, they do not offer it.
  3. If equivalent evidence may be accepted, collect it early. Surespan’s guidance is to request the Declaration of Performance, test reports and factory production control certification that match EN 12101-2.
  4. Use the right area in the calculation. Geometric and aerodynamic areas are different numbers. Confirm which one the engineer’s method calls for.
  5. Design the power and controls. An actuator-driven vent needs its control panel, battery backup, fire alarm interface and cabling specified, not assumed.

If your project needs UL-listed vents, settle that before a European vent goes on the drawings. The same US and European question for roof hatches is covered in Fire Rating Standards for Roof Hatches in the US, and for skylights in Comparing US and EU Standards for Skylights.

Frequently asked questions

Is UL 793 the same as EN 12101-2?

No. Both are product standards for smoke vents, but they are separate documents with their own scope and tests. UL 793’s scope covers mechanically-opened and gravity-opened vents whose automatic operation does not depend on electrical power. EN 12101-2 covers natural smoke and heat exhaust ventilators and classifies them for properties such as wind, snow, low temperature and heat.

What is NFPA 204?

NFPA 204, Standard for Smoke and Heat Venting, is the NFPA design standard for smoke and heat venting. It is a design document for the building, not a product listing.

Are Surespan smoke vents UL 793 listed?

The data sheets do not state a UL listing. They state testing and CE marking to EN 12101-2.

Can a smoke vent be used for everyday ventilation?

Some European vents also open for daily ventilation: the SRH-PAOV sheet lists daily ventilation and access. UL 793 says the vents it covers are not intended for use as general purpose building ventilation devices.

Who decides whether a CE marked vent is acceptable in the US?

The authority having jurisdiction, on the advice of the project’s fire protection engineer.

See the full smoke vent range and the smoke vent resources. To discuss a project, use the Surespan contact page.

Sources

  • Surespan data sheet “Thermally Broken AOV” (SRH-PAOV), revision mark REV 1.0 (06/22), June 2022: actuator, controls, CE marking, daily ventilation and access. Product page: Smoke Vent with Access.
  • Surespan data sheet “Bespoke Smoke Vent” (SRH-AOV), revision mark REV 1.0 (06/22), file dated October 2026: CE marking, geometric and aerodynamic areas. Product page: Custom Smoke Vent.
  • Surespan data sheet “Smoke Vent SRHPAOV” (SRHP/AOV), RF REV 3 05/18, May 2018: EN 12101-2 classes, control panel. Range: Smoke Vents.
  • UL 793, Automatically Operated Roof Vents for Smoke and Heat, Edition 4, shopulstandards.com.
  • NFPA 204, Standard for Smoke and Heat Venting, nfpa.org.

Robert Fletcher

Rob leads Surespan’s global specification efforts, translating access requirements into permit-ready, code-compliant solutions across hatches, covers, ladders, vents, and skylights. He manages submittals and approvals to keep projects moving through permitting the first time.