A BMS-ready roof hatch, smoke vent or floor access door is not itself part of the building management system, or building automation system (BAS). It is a unit specified with the right actuators, control panel and switch contacts so that the controls contractor can connect it to the BAS. The Surespan smoke vent and floor hatch sheets quoted below give 24 V DC actuators and control panels with battery backup, and the key switches give simple contacts. Turning those signals into BACnet or Modbus is usually done by an I/O interface module from the controls team, not by the hatch.
This guide is for architects, MEP engineers and controls contractors who need roof and floor access products to fit a building controls strategy without overspecifying them.
What does “BMS-ready” actually mean?
Writing “BMS connection required” on a hatch schedule rarely means the hatch arrives speaking a network protocol. It means the access package is specified with actuation and wiring that the specialist controls team can integrate.
Topic |
The common assumption |
How it works in practice |
|---|---|---|
Protocol |
The hatch plugs straight into BACnet or Modbus |
The actuator works on 24 V signals or volt-free contacts; the controls team provides the I/O interface module |
Logic |
A “smart hatch” handles all the logic itself |
Cause and effect is managed by the external control panel and the BAS |
Smoke venting |
A powered roof hatch is a smoke vent |
A smoke vent is a life-safety product tested as one; the smoke vent with access sheet states CE marking to EN 12101-2 |
Sizing |
One cut-out guide fits every product |
Each product family needs its own rough opening and clear opening coordination |
When should a roof hatch be electrically operated?
A manual hatch with gas spring assisted opening is still the right answer for occasional, straightforward access. Move to an electric hatch when one of these applies:
- The opening is oversized or needs a double leaf.
- Roof access is restricted to authorized staff.
- The opening is part of a managed maintenance or exit route.
- The client wants remote, grouped or battery-backed operation.
On Surespan’s data sheets, the standard roof hatch (SRHP75), the double leaf hatch (SRHP/DL) and the fire rated hatch (SRHTB/FR) list electric opening and a concealed actuator as options, and the sliding roof hatch (SLHP) offers manual or electric opening. The solar powered roof hatch (SRHP-SOLAR) has an electric actuator powered by a 20w semi-flexible solar panel, operated by wireless remote control, with battery backup allowing up to 7 operations per day.
On large projects the hatch becomes part of the operating logic. At Education City Stadium, eight thermally broken hatches of 4000 x 1400 mm (157.5 x 55.1 in) open on synchronized 24 V DC actuators with battery-backed systems. At Kielder Observatory, double leaf hatches are electrically operated, remotely controlled and sequenced to open in order. Once a hatch does more than give occasional access, the specification has to cover the product and its operating logic.
Smoke vents: where loose terms cost the most
“Powered access hatch”, “automatic smoke vent” and “hatch linked to the BMS” sound alike and lead to very different products. If smoke control is in scope, the conversation moves to tested smoke vents and to the fire alarm designer. A powered access hatch uses its actuators for convenience or access control; a smoke vent is a life-safety device with its own tested performance and fire-mode operation.
Surespan’s smoke vent with access (SRH-PAOV) sheet gives a 24V DC/4A actuator and lists these controls: a 24V control center, a fireman’s switch (the sheet’s term for a firefighter’s switch), a key switch, a push button and a smoke detector. The 2018 SRHP/AOV sheet adds a 24VDC control panel with 72 hour battery backup, control panels for a maximum total load of 8A, 24A, 30A or 32A, and 48VDC also available.
Whether a CE marked European vent is accepted on a US project is for the authority having jurisdiction to decide, on the fire protection engineer’s advice. Settle that, and the fire alarm interface, before the vent goes on the controls drawings.
What switches and detectors connect to the control panel?
Device (code) |
What the data sheet states |
|---|---|
Key switch (SP1161) |
2 N/O contact blocks rated at 230 V AC, 16 A; IP54; supplied with a 30/10 euro half cylinder and 2 keys; surface mounted |
Externally rated key switch (SP1161-A) |
2 N/O contact blocks rated at 230 V AC, 16 A; IP66, for internal or external use; 3 position cylinder with 2 keys; surface mounted |
Comfort switch (SP1322-A) |
Daily ventilation button, internal use only, IP40. As standard, one press opens the hatch for a set time and closing runs for double that time; for access use, the panel is set to Pulse Constant so the hatch moves only while the switch is pressed |
Smoke detector (SP1322-B) |
24 V DC, 0.1 mA at rest, internal use only; the end of line resistor moves from the control panel to the last detector |
Fire breakglass (SP1322-C) |
Internal use only, IP40; break the glass and press the red fire button, reset with the black button; LEDs show green when the hatch is closing, yellow on a control panel error and red when it opens on fire |
“N/O” means normally open: the contact closes when the switch is turned. Contacts like these are what an I/O module reads. Use a key switch where opening the hatch is a safety or security risk and must be limited to authorized users, and a push button where everyday operation is safe and separate from the emergency logic.
Floor access doors: where controls meet structure
A floor access door stops being a simple lid once the brief adds heavy stone infill, an exit route or remote plant. Surespan’s recessed (HIAC) and flush (SAC) floor hatch sheets offer manual, electric or hydraulic operation. Smaller sizes use gas spring assisted opening; larger hatches are electric or hydraulic, depending on loading, infill and size.
- Electric: actuators lock in position, and the control panel has 72 hour battery backup for emergencies. The flush hatch drawing shows a single leaf opened by 2 off 24V DC synchronized actuators. Listed options include removable actuators, internal or external key switches and push buttons, and bespoke switches such as key pads and remote control.
- Hydraulic: hydraulic actuators, a manual hand pump or electrically driven options, with bespoke additions such as alarms, a klaxon and contact sensors.
Plan the rough opening from the clear opening you need. Frames, gas springs, safety grids and actuators take space inside the opening, so a 1000 x 1000 mm (39.4 x 39.4 in) rough opening may not pass a piece of plant that is 900 x 900 mm (35.4 x 35.4 in). At the Marina East Desalination Plant, electrically operated flush floor covers for 4000 x 1400 mm (157.5 x 55.1 in) structural openings were run from SP1185/C control panels, SP1165 selector switches and wireless remote fobs.
The coordination matrix
Factor |
Roof hatches |
Smoke vents |
Floor access doors |
|---|---|---|---|
Sizing |
Rough opening vs clear opening |
Aerodynamic free area |
Clear opening, allowing for actuators |
Interface |
Curb height, roof build-up |
Wind deflectors, geometry |
Recess depth, infill weight, drainage |
Actuation |
24 V DC, synchronized pairs |
Fail-safe operation, tested opening |
Hydraulic power packs, electric assist |
Controls |
Key switch or push button |
Fire alarm interface, reset logic |
Remote plant location, safety edge |
Monitoring |
Open or closed status to the BAS |
Fault, position and power-loss feedback |
Open or closed status, authorized local operation |
Safety and standby |
Ladders, guardrails |
Standby power, battery backup |
Safety grids, hinged rails |
For data halls and other critical facilities, see the data centers sector.
Frequently asked questions
Can a roof hatch connect directly to BACnet or Modbus?
Usually not. Automated hatches use 24 V polarity reversal or volt-free contacts. The controls contractor provides an I/O interface module that translates those signals into the BAS protocol.
Is an electrically operated roof hatch a smoke vent?
No. A powered access hatch uses actuators for convenience or access control. A smoke vent is a life-safety product tested for its opening, fire-mode operation and aerodynamic performance.
What happens to an electric hatch in a power cut?
The recessed and flush floor hatch sheets and the 2018 SRHP/AOV smoke vent sheet list a control panel with 72 hour battery backup. The solar powered roof hatch has its own battery and solar panel. For any other unit, ask for the standby arrangement in writing.
What should be in the submittal before commissioning?
The product data sheet, rough opening drawings, BIM models for clash detection, and the wiring diagrams for the actuator and the control panel.
Data sheets, drawings and wiring diagrams are in the Resource Centre. See the roof hatches, smoke vents and floor hatches. To discuss a controls brief, use the Surespan contact page.
Sources
- Surespan data sheet “Thermally Broken AOV” (SRH-PAOV), REV 1.0, June 2022: actuator, controls, CE marking. Product page: Smoke Vent with Access.
- Surespan data sheet “Smoke Vent SRHPAOV” (SRHP/AOV), revision mark RF REV 3 05/18, May 2018: control panel, battery backup, load options, 48VDC. Range: Smoke Vents.
- Surespan data sheet “Thermally Broken Roof Hatch” (SRHP75), May 2021: electric opening and concealed actuator options. Product page: Standard Roof Hatch.
- Surespan data sheet “Thermally Broken SLHP (Telescopic) Sliding Hatch”, REV 2.0, March 2022: manual or electric opening. Product page: Sliding Roof Hatch.
- Surespan data sheet “Solar Powered Roof Hatch” (SRHP-SOLAR), REV 1.0, November 2021: solar panel actuator, wireless remote, battery backup. Product page: Solar Powered Roof Hatch.
- Surespan data sheets “Recessed Floor Hatch” (HIAC), revision mark REV 1.0 (04/21), file dated March 2022, and “Flush Floor Hatch” (SAC), REV 1.0, July 2022: operation, electric and hydraulic controls. Product pages: Recessed Floor Hatch, Flush Floor Hatch.
- Surespan data sheets for the SP1161 key switch (January 2020), SP1161-A key switch (January 2022), SP1322-A comfort switch (August 2021), SP1322-B smoke detector (May 2020) and SP1322-C fire breakglass (August 2021). Resources: Smoke Vent Resources.