A U-value on a roof hatch, smoke vent or skylight data sheet can describe four different things: the insulation in the lid and curb, the glass alone, the whole unit including its frame, or the unit as installed in a particular roof. Only values on the same basis can be compared. Before you put two suppliers’ figures side by side, get each one to say in writing which of the four it is, at what size, and what is included at the edges.
This guide covers commercial roof hatches, smoke vents and glazed roof access units. It explains how to read the figures; it does not cover how your energy code treats a roof hatch, which is a question for the energy consultant.
What can a “U-value” on a data sheet refer to?
Basis |
What it describes |
Where you see it |
|---|---|---|
Insulation core |
The insulation board in the lid and curb, on its own |
Solid roof hatches and insulated smoke vents |
Ug, center of glass |
The glass only, away from the edges and the frame |
Glazed hatches, glazed smoke vents and skylights |
Uw, whole unit |
The whole assembly, including frame, spacers and edges |
Glazed products, and any product with a declared whole-unit value |
Installed |
The unit in a defined roof build-up and curb detail |
Project calculations, not product sheets |
A component value is useful for understanding the build-up. It is not a whole-unit figure, and it is not comparable with one. If an energy consultant asks for a hatch’s U-value, the whole-unit basis is almost always the one they need.
US documents often give heat transfer as a U-factor in Btu/h·ft²·°F, and insulation as an R-value, a thermal resistance, where a higher figure means less heat flow. Surespan’s sheets print U-values in W/m²K. Ask the supplier to state the value in the units your model uses, on the same basis, rather than converting a component figure yourself.
What do Surespan’s data sheets actually state?
Every value below is a component value, as the sheet prints it. None is a whole-unit U-value.
Product (model) |
Value on the sheet |
What it is the U-value of |
|---|---|---|
Standard roof hatch (SRHP75) |
0.28 W/m²K |
The 75 mm (3.0 in) polyiso (PIR) insulation in the lid and curb |
Sliding roof hatch (SLHP) |
0.43 W/m²K |
The 50 mm (2.0 in) polyiso insulation |
Solid lid smoke vent with access (SRHP/AOV) |
0.43 W/m²K or 0.63 W/m²K |
The 50 mm (2.0 in) polyiso, or the 50 mm (2.0 in) non-combustible mineral wool option |
Fire rated roof hatch (SRHTB/FR) |
0.63 W/m²K |
The mineral wool insulation |
Glazed smoke vent (SRHG-AOV) |
1.4 W/m²K |
The 31.5 mm (1.2 in) sealed double glazed unit |
Boxed glazed roof access (BG) |
1.5 W/m²K |
The 35.5 mm (1.4 in) sealed double glazed unit |
Dome smoke vent (SDP-MD-50) |
from 1.65 W/m²K |
The triple layer polycarbonate dome lid |
Read the table as it is labelled. The 0.28 W/m²K of the SRHP75 and the 1.4 W/m²K of the glazed vent’s glass unit are not a ranking of the two products: one is an insulation board, the other a glazed unit, and neither includes the frame.
What does “thermally broken” mean, and what does it not mean?
A thermal break interrupts a conductive path, usually through the frame and curb, where an aluminum section would otherwise carry heat straight from inside to outside. It reduces thermal bridging at the perimeter. Surespan’s standard, double leaf and fire rated roof hatch sheets describe a thermally broken lid and curb.
Three things it does not tell you:
- It is not insulation. A thermally broken hatch still needs its insulation thickness, material and continuity confirmed.
- It is not a U-value. It describes how the hatch is built, not the declared performance.
- It is not the whole interface. A break in one part of the build-up does not make the installed junction with the roof thermally continuous.
If a tender asks “is it thermally broken?”, add: “Please provide a typical section showing where the thermal break runs through the lid, curb and frame.”
Glazed units: Ug or Uw?
With glazed roof access units and glazed smoke vents, the usual trap is not the units. It is the scope. Ug, the center-of-glass value, covers the glass only and leaves out the frame and edge effects. Uw covers the whole assembly, frame and spacers included. A headline about glass performance can sit beside a higher whole-unit figure once the frame is counted. Never accept a glazed unit’s U-value without asking which of the two it is.
Installation can create the thermal bridge
A well insulated, thermally broken hatch can still underperform if the roof junction is badly detailed. Surespan’s fitting guidance for its roof hatches says the units are made with an integral insulated curb and an external fixing flange, and that the foot of the fixing flange should be insulated after the unit is fixed, before the roof membrane is dressed up the sides and sealed under the weathering lip. When comparing suppliers, ask what each declared value assumes at the flange, the curb and the roof insulation junction.
The like-for-like checklist for tender questions
- What does the U-value refer to? Insulation core, Ug, Uw or installed. Ask for the label in writing.
- Is it a component or a whole-unit value? Component figures cannot be compared with whole-unit ones.
- At what size and configuration? Size and frame proportion change the result. Ask for the reference size and whether custom sizes differ.
- What is included at the perimeter? Frame, edges and curb liner: included or excluded.
- Does it include the curb? The manufacturer’s curb and a builder’s curb behave differently.
- Where is the thermal break? Ask for a section with the break marked.
- What is the calculation basis? Ask for the report or calculation behind the figure, with its inclusions and exclusions.
Where do hatch U-values matter most?
- Heated stair cores and conditioned top floors where the hatch opens into occupied space.
- Plant rooms and spaces where the hatch or vent sits directly over a conditioned area.
- Glazed access units, where Ug and Uw are easily confused.
- Projects sensitive to condensation at cold bridges, at the frame and the perimeter.
For the same comparison problem on skylights, see Comparing US and EU Standards for Skylights.
Frequently asked questions
Is the U-value on a roof hatch data sheet for the whole hatch?
Not on the Surespan sheets in the table above. The values for solid hatches and vents are those of the insulation in the lid and curb; the glazed values are those of the glazed unit or dome lid. Ask any supplier to say whether a figure is a component or a whole-unit value.
Is a thermally broken roof hatch an insulated roof hatch?
Not by definition. A thermal break interrupts heat flow through the frame; insulation is a separate layer with its own thickness and value. Check both.
Does the U-value stay the same at every size?
Not always. Size and frame proportion can change the result. Ask for the reference size behind a declared value.
Is a lower U-value always the better hatch?
Only for heat loss through the insulation. The choice of insulation also has a fire side: the SRHP/AOV sheet offers non-combustible mineral wool at 0.63 W/m²K beside polyiso at 0.43 W/m²K.
See the full roof hatch range and the glazed hatches. To ask for the thermal data behind a figure, use the Surespan contact page.
Sources
- Surespan data sheet “Thermally Broken Roof Hatch” (SRHP75), May 2021: 75 mm polyiso insulation U-value, thermally broken lid and curb. Product page: Standard Roof Hatch.
- Surespan data sheet “Double Door Roof Hatch SRHP/DL”, revision mark REV 1.0 (04/21), file dated July 2022: thermally broken lid and curb. Product page: Double Leaf Roof Hatch.
- Surespan data sheet “Thermally Broken SLHP (Telescopic) Sliding Hatch”, REV 2.0, March 2022: 50 mm polyiso insulation U-value. Product page: Sliding Roof Hatch.
- Surespan data sheet “Smoke Vent SRHPAOV” (SRHP/AOV), revision mark RF REV 3 05/18, May 2018: polyiso and mineral wool insulation U-values. Range: Smoke Vents.
- Surespan data sheet “Fire Rated Roof Hatch” (SRHTB/FR), March 2026 (revision mark REV 2.0, 06/22): mineral wool insulation U-value, thermally broken lid and curb. Product page: Fire Rated Roof Hatch.
- Surespan data sheet “Glazed Smoke Vent” (SRHG-AOV), revision mark REV 1.0 (06/22), file dated October 2026: sealed double glazed unit and its U-value. Product page: Glazed Smoke Vent.
- Surespan data sheet “Boxed Glazed Roof Access” (BG), October 2018: sealed double glazed unit and its U-value. Range: Glazed Hatches.
- Surespan data sheet “Polycarbonate Dome AOV” (SDP-MD-50), September 2025: polycarbonate dome lid U-value. Product page: Dome Smoke Vent.