The geometric free area of a smoke vent is the physical opening: the width times the length of the opening, measured at right angles to the airflow, with no allowance for how well air actually flows through it. The aerodynamic free area is the effective area for smoke exhaust, found by testing to EN 12101-2: the geometric area multiplied by a coefficient of discharge between 0 and 1. The aerodynamic area is therefore normally the smaller figure, and a smoke vent data sheet that prints both is telling you two different things.
European vents, including Surespan’s, are tested to EN 12101-2 and their data sheets use these two terms. In the US, the product standard for automatically operated roof vents is UL 793 and smoke and heat venting is designed under NFPA 204. Whichever framework applies, the first question is the same: which area does the engineer’s calculation use?
What is the geometric free area?
Surespan’s guide defines the geometric area as the actual physical opening in the roof or wall, measured perpendicular to the airflow, without considering any installed ventilation products. It is plain arithmetic. A vent with an opening of 1.26m x 1.26m (49.6 x 49.6 in) has a geometric area of 1.26 x 1.26 = 1.5876 m².
The geometric area says how big the hole is. It says nothing about the lid standing in the airflow, the opening angle, the curb, or wind blowing across the roof.
What is the aerodynamic free area?
The aerodynamic free area is the area that is actually effective for smoke extraction. It is determined under test conditions specified in EN 12101-2, and it is calculated as:
Aerodynamic area = geometric area x coefficient of discharge (Cv)
The coefficient of discharge is a measure of the vent’s efficiency, found by testing. It accounts for the vent’s design, its opening angle, and the presence of wind deflectors or other obstructions, and it typically ranges between 0 and 1. A higher coefficient means better airflow through the same opening.
How do the two figures compare on a real data sheet?
The data sheet for Surespan’s custom smoke vent (SRH-AOV) prints both areas for each standard size. The geometric area is given without wind deflectors and the aerodynamic area to EN12101-2 with wind deflectors:
Product code |
Size |
Actuator |
Geometric area (without wind deflectors) |
Aerodynamic area, EN12101-2 (with wind deflectors) |
|---|---|---|---|---|
SRH-AOV/125.125 |
1250 x 1250 mm (49.2 x 49.2 in) |
Single |
1.56m² |
0.93m² |
SRH-AOV/150.120 |
1500 x 1200 mm (59.1 x 47.2 in) |
Single |
1.80m² |
1.12m² |
SRH-AOV/200.120 |
2000 x 1200 mm (78.7 x 47.2 in) |
Single |
2.40m² |
1.58m² |
SRH-AOV/250.180 |
2500 x 1800 mm (98.4 x 70.9 in) |
Twin |
4.50m² |
2.98m² |
SRH-AOV/300.180 |
3000 x 1800 mm (118.1 x 70.9 in) |
Twin |
5.40m² |
3.60m² |
Read the two columns with care: they describe different set-ups, one without wind deflectors and one with them, so dividing one by the other does not give a published coefficient of discharge. For a calculation, use the declared figure for the exact model, size and configuration, not a ratio worked out from a table.
Why does the difference matter?
- Specification. When you select a vent, you need to know whether the required area is geometric or aerodynamic. Meeting a geometric figure does not meet an aerodynamic requirement of the same number.
- Performance. The aerodynamic area is the better guide to how much smoke a vent can actually move, because it is measured, not drawn.
- Comparison. Two vents with the same opening can have different aerodynamic areas. Compare aerodynamic with aerodynamic, for the same size and the same configuration.
When a smoke vent is specified by a fire engineer, Surespan’s guide notes, it will usually be given as an aerodynamic free area. The matching geometric area will then be larger. A schedule that gives only an area in square meters leaves that question open, so write the area type next to the number.
How should a US team read a European smoke vent data sheet?
- Ask the engineer which area the calculation uses. Do this before comparing vents from different sources. Some documents also use the term “net free area”: ask which definition is meant.
- Check the column headings. On the SRH-AOV sheet, the geometric area is without wind deflectors and the aerodynamic area is with them. Make sure the vent you order matches the configuration behind the figure you use.
- Match the size. Areas are given per size code. An area for one size does not scale to another.
- Ask for the test evidence. An aerodynamic area is a test result. Ask for the report for the exact model and size.
- Settle the listing question separately. An EN 12101-2 aerodynamic area is a European test figure. Surespan’s data sheets do not claim a UL 793 listing, and the authority having jurisdiction decides what evidence it accepts.
Frequently asked questions
Which is larger, geometric or aerodynamic free area?
The geometric area. The aerodynamic area is the geometric area multiplied by a coefficient of discharge, which typically ranges between 0 and 1, so it is normally smaller.
What is the coefficient of discharge?
A measure of how efficiently air passes through the vent, found by testing. It accounts for the vent’s design, opening angle and any wind deflectors or obstructions, and typically ranges between 0 and 1.
How do you calculate geometric free area?
Multiply the width by the length of the opening, measured at right angles to the airflow. For a 1.26m x 1.26m (49.6 x 49.6 in) opening that is 1.5876 m².
Can you calculate aerodynamic free area yourself?
Only if you have a tested coefficient of discharge for that vent in that configuration. In practice, use the aerodynamic area the manufacturer declares from its EN 12101-2 testing.
See the full smoke vent range, including the smoke vent with access, and the smoke vent resources. To ask about areas for a specific size, use the Surespan contact page.
Sources
- Surespan data sheet “Bespoke Smoke Vent” (SRH-AOV), revision mark REV 1.0 (06/22), file dated October 2026: sizes, actuators, geometric and aerodynamic areas. Product page: Custom Smoke Vent.
- UL 793, Automatically Operated Roof Vents for Smoke and Heat, Edition 4, shopulstandards.com.
- NFPA 204, Standard for Smoke and Heat Venting, nfpa.org.