A smoke vent, also called a smoke hatch or a smoke and heat vent, is a powered or self-opening cover in a building’s roof that opens automatically in a fire so that smoke and hot gases can escape. In the United States the product standard for these vents is UL 793, Automatically Operated Roof Vents for Smoke and Heat, and NFPA 204, Standard for Smoke and Heat Venting, is the design standard. In Europe the product standard is EN 12101-2, and that is the standard Surespan’s smoke vents are tested and CE marked to.
This guide is about smoke vents in the roofs of commercial, institutional and multifamily buildings. It does not cover vehicle or RV roof vents.
What does a smoke vent do in a fire?
In a building fire the smoke is often more dangerous than the flames. A vent at the top of a stairwell or a large open space lets smoke rise out of the building instead of filling it. That helps in three ways:
- escape routes stay clearer of smoke for longer, so occupants can get out;
- firefighters get a clearer area to work from and can tackle the fire earlier;
- less smoke spreads through the building, so smoke damage is reduced.
A smoke vent is one part of a smoke control design. Where it goes, how big it is and what opens it are decided by the fire protection engineer and the code that applies to the building, not by the vent itself.
How does a smoke vent work?
A typical roof smoke vent has an insulated curb fixed to the roof, a hinged lid, and one or more actuators that push the lid open. The actuators are wired to a control panel. When a smoke detector, a push button or the firefighter’s switch triggers the panel, the actuators open the lid.
On Surespan’s vents the control side is a low voltage system. The data sheets for the dome smoke vent (SDP-MD-50) and the smoke vent with access (SRH-PAOV) list a 24V DC/4A actuator and these controls: a 24V control center, a fireman’s switch (firefighter’s switch), a key switch, a push button and a smoke detector. The 2018 sheet for the SRHP/AOV solid lid vent adds a control panel with 24VDC, 72 hour battery back up.
Many vents also open a little on a normal day for fresh air. The sheets call this comfort ventilation or daily ventilation. It uses the same actuator, controlled by a push button or the building’s controls.
Which standards apply to smoke vents in the US?
Document |
What it is |
|---|---|
UL 793, Automatically Operated Roof Vents for Smoke and Heat (Edition 4) |
The US product standard. Its scope covers automatically operated roof vents for smoke and heat in two general categories, mechanically opened and gravity opened, and says these vents are not intended for use as general purpose building ventilation devices. |
NFPA 204, Standard for Smoke and Heat Venting |
The design standard for smoke and heat venting, published by NFPA. |
EN 12101-2 |
The European product standard for natural smoke and heat exhaust ventilators. Surespan’s smoke vent data sheets state CE marking to EN12101-2. |
Whether a building needs smoke vents at all, and how many, is set by the building and fire codes your jurisdiction has adopted. Check that with the fire protection engineer and the authority having jurisdiction early in design.
Surespan’s data sheets do not claim a UL 793 listing. The evidence they offer is testing and CE marking to EN 12101-2. If your project or your jurisdiction calls for a UL 793 listed vent, that has to be settled before a European tested vent is specified. The authority having jurisdiction decides what it accepts.
What do the EN 12101-2 classes on a data sheet mean?
EN 12101-2 sorts vents into classes for the conditions they are tested under. The 2018 sheet for Surespan’s SRHP/AOV solid lid vent prints these, and notes that they apply to the SRHP/AOV only and that other models may differ:
Property tested |
Class printed on the SRHP/AOV sheet |
|---|---|
Snow load |
SL500 |
Low ambient temperature |
T (-15°) |
Wind load |
WL1500 |
Resistance to heat |
B300 |
When you compare vents, compare the classes for the same property, and ask for the classes of the exact model and size you are specifying.
Geometric area or aerodynamic area: which one counts?
Smoke vent data sheets often print two areas for the same vent. The geometric area is the clear opening. The aerodynamic area is the effective area measured in an EN 12101-2 test, which is smaller, because air does not flow through the full opening. On the custom smoke vent sheet (SRH-AOV), for example, the SRH-AOV/150.120 at 1500 x 1200 mm (59.1 x 47.2 in) has a geometric area of 1.80m² without wind deflectors and an aerodynamic area of 1.12m² with wind deflectors.
A smoke control calculation is done with one of these, so make sure the figure on the data sheet is the one your engineer’s method uses.
What types of smoke vent are there?
Type |
What the data sheet states |
|---|---|
Dome smoke vent (SDP-MD-50) |
Triple layer polycarbonate dome lid. 50 mm (2.0 in) polyiso insulation in the curb, 0.43 W/m²K, available at no extra cost. Can be installed up to 15° pitch. |
Glazed smoke vent (SRHG-AOV) |
Double glazed lid with a 6mm Pilkington toughened outer pane and a 9.5mm toughened and laminated inner pane, unit U-value 1.4W/m²K. 24V DC/10A (max) actuator with electro-magnetic locking. Sizes up to 3000 x 1400mm (118.1 x 55.1 in), up to 30° pitch. |
Smoke vent with access (SRH-PAOV) |
Insulated aluminum lid that also gives daily ventilation and access to the roof. 300mm (11.8 in) curb with 50mm polyiso insulation to 0.43 W/m²K. Sizes up to 1260 x 1260 mm (49.6 x 49.6 in), up to 15° pitch. |
Custom smoke vent (SRH-AOV) |
Insulated aluminum lid, sizes up to 3000 x 1800mm (118.1 x 70.9 in), single or twin actuators, up to 30° pitch. |
Exi-Vent roof hatch (SV-EXI) |
A roof access hatch and a separate smoke vent side by side, split by a minimum 150mm (5.9 in) rain gutter. In one example on the sheet the two units can be operated independently. Made to any size. |
The 0.43 W/m²K figures are values of the polyiso insulation, and 1.4W/m²K is the value of the glazed unit. None of them is the U-value of the complete vent. Ask for a whole-unit value if your energy model needs one.
Is a smoke vent the same as a roof hatch?
No. A standard roof hatch is built for people to pass through and is not a smoke vent. A smoke vent opens automatically on a fire signal. Where one opening has to do both jobs, choose a product made for both: the smoke vent with access opens for daily access and ventilation as well as for smoke, and the Exi-Vent puts a separate access hatch and smoke vent in one frame. For roof hatches themselves, see the roof hatch range.
Frequently asked questions
What is the difference between a smoke vent and a smoke hatch?
None in practice. Smoke hatch, smoke vent, roof smoke vent and smoke and heat vent are used for the same product. The UK term automatic opening vent, or AOV, means the same thing and appears on Surespan’s product codes.
Can a smoke vent be used for everyday ventilation?
Many can be opened for comfort ventilation, as Surespan’s sheets describe. That does not make a smoke vent a general ventilation device: UL 793 says the vents it covers are not intended for that use.
Are Surespan smoke vents UL listed?
The data sheets do not state a UL listing. They state CE marking to EN 12101-2. Agree the acceptable evidence with the authority having jurisdiction before you specify.
Can a smoke vent go on a pitched roof?
Within limits. The dome vent and the smoke vent with access sheets say up to 15° pitch, and the glazed, custom and Exi-Vent sheets say up to 30° pitch.
For the full range see Smoke Vents and the smoke vent resources. To ask about a specification, use the Surespan contact page.
Sources
- Surespan data sheet “Polycarbonate Dome AOV” (SDP-MD-50), September 2025: lid, actuator, controls, insulation option, pitch. Product page: Dome Smoke Vent.
- Surespan data sheet “Thermally Broken AOV” (SRH-PAOV), REV 1.0, June 2022: actuator, controls, curb, insulation, sizes, pitch. Product page: Smoke Vent with Access.
- Surespan data sheet “Glazed Smoke Vent” (SRHG-AOV), REV 1.0, June 2022 (file dated October 2026): glazing, actuator, sizes, pitch. Product page: Glazed Smoke Vent.
- Surespan data sheet “Bespoke Smoke Vent” (SRH-AOV), REV 1.0, June 2022 (file dated October 2026): sizes, areas, pitch. Product page: Custom Smoke Vent.
- Surespan data sheet “Exi-Vent” (SV-EXI), REV 1.0, June 2022: layout, gutter, sizes, pitch. Product page: Exi-Vent Roof Hatch.
- Surespan data sheet “Smoke Vent SRHPAOV” (SRHP/AOV), RF REV 3, May 2018: EN 12101-2 classes, control panel. Range: Smoke Vents.
- UL 793, Automatically Operated Roof Vents for Smoke and Heat, Edition 4, shopulstandards.com.
- NFPA 204, Standard for Smoke and Heat Venting, nfpa.org.